View larger
UKK 5-TG 3007042 PHOENIX CONTACT Disconnect terminal block
UKK 5-TG
3007042
PHOENIX CONTACT
50 Pcs.
Automation > (Knife) disconnect terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A disconnect terminal block like the Phoenix Contact UKK 5-TG provides multi-level signal management with built-in isolation capabilities for complex industrial control panels. Electrical professionals utilize these components to save valuable rail space while maintaining easy access for testing and circuit interruption. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.2 mm²
- Connectable conductor cross section multi-wired (EF007343): 0.2 mm²
- Rated current In (EF008250): 26 A
- Rated voltage (EF000228): 400 V
- Type of electrical connection 1 (EF002526): Screw connection
- Type of electrical connection 2 (EF002527): Screw connection
- Number of clamp positions per level (EF002660): 2
- Internally connected stages (EF002661): Yes
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Width (EF000008): 6.2 mm
- Height (EF000040): 80 mm
- Depth (EF000049): 56 mm
- Closing plate required (EF002525): No
- Colour (EF000007): Grey
- With integrated test socket (EF002547): No
More info
▲Key Commercial Data
| Orderkey | 3007042 |
|---|---|
| Packing unit | 50 pc |
| Catalog page | Page 471 (C-1-2017) |
| GTIN | 4017918091491 |
| Weight per Piece (excluding packing) | 23.580 g |
| Custom tariff number | 85369010 |
| Country of origin | TR (Turkey) |
General
| Number of levels | 2 |
|---|---|
| Number of connections | 4 |
| Nominal cross section | 4 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V2 |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Connection in acc. with standard | IEC 60947-7-1 |
| Nominal current IN | 26 A |
| Maximum load current | 26 A (with 4 mm² conductor cross section) |
| Nominal voltage UN | 400 V |
| Open side panel | No |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 7.3 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.2 mm² / 0.2 kg |
| 4 mm² / 0.9 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.2 mm² |
| Tractive force setpoint | 10 N |
| Conductor cross section tensile test | 4 mm² |
| Tractive force setpoint | 60 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 32/NS 35 |
| Setpoint | 1 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 0.48 kA |
| Conductor cross section short circuit testing | 1.5 mm² |
| Short-time current | 0.18 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -40 °C |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
| 2 conductors with same cross section, solid min. | 0.2 mm² |
| 2 conductors with same cross section, solid max. | 1.5 mm² |
| 2 conductors with same cross section, stranded min. | 0.2 mm² |
| 2 conductors with same cross section, stranded max. | 1.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.25 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 1.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 2.5 mm² |
| Cross section with insertion bridge, solid max. | 4 mm² |
| Cross section with insertion bridge, stranded max. | 4 mm² |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Internal cylindrical gage | A4 |
| Screw thread | M3 |
| Tightening torque, min | 0.6 Nm |
| Tightening torque max | 0.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V2 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |