Serving as a distributed signal interface, the Phoenix Contact RAD-DO8-IFS 2902811 PHOENIX CONTACT I/O extension module expands communication capabilities within wireless and remote automation setups. I/O extension modules are frequently integrated into industrial networks to accommodate extra signal points without redesigning existing control architectures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 0
- Number of digital outputs (EF001993): 8
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Type of voltage (input voltage) (EF003033): DC
- Output current (EF003202): 0.2 A
- Short-circuit protection, outputs available (EF003203): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces parallel (EF003026): 0
More info
▲Key Commercial Data
| Orderkey | 2902811 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 461 (C-6-2017) |
| GTIN | 4046356681544 |
| Weight per Piece (excluding packing) | 211.000 g |
| Custom tariff number | 85177000 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C |
| -40 °F ... 158 °F | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| -40 °F ... 185 °F | |
| Permissible humidity (operation) | 20 % ... 85 % |
| Permissible humidity (storage/transport) | 20 % ... 85 % |
| Altitude | 2000 m |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Shock | 16g, 11 ms |
General
| Overvoltage category | II |
|---|---|
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Degree of pollution | 2 |
| Housing material | PA 6.6-FR |
| Flammability rating according to UL 94 | V0 |
| MTTF | 1594 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 600 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| 230 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
Supply
| Supply voltage range | 19.2 V DC ... 30.5 V DC (DIN rail connector) |
|---|---|
| Max. current consumption | ≤ 22 mA (At 24 V DC, at 25°C) |
| Transient surge protection | Yes |
Digital outputs
| Number of outputs | 8 |
|---|---|
| Contact type | Transistor |
| Supply voltage range | 12 V DC ... 30.5 V DC (for digital outputs) |
| Maximum switching voltage | 30.5 V DC |
| Max. switching current | 200 mA (per channel) |
| Output current when switched off | ≤ 300 µA |
| Output voltage when switched off | ≤ 2 V |
| Maximum switching frequency | 10 Hz |
| Behavior of the outputs (adjustable via DIP switch) | Hold / Reset |
Electrical isolation
| Digital I/O | 50 V (Rated insulation voltage (between the channel groups 1...4 and 5...8/TBUS supply, reinforced insulation according to EN 61010)) |
|---|
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Tightening torque | 0.6 Nm |
| Screw thread | M3 |
Status indicator
| Status display | Green LED (supply voltage, PWR) |
|---|---|
| Green LED (bus communication, DAT) | |
| Red LED (periphery error, ERR) | |
| Yellow LED (digital output, DO1) | |
| Yellow LED (digital output, DO2) | |
| Yellow LED (digital output, DO3) | |
| Yellow LED (digital output, DO4) | |
| Yellow LED (digital output, DO5) | |
| Yellow LED (digital output, DO6) | |
| Yellow LED (digital output, DO7) | |
| Yellow LED (digital output, DO8) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-2 |
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-4 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN 60079-0 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN-60079-15 |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Flammability rating according to UL 94 | V0 |
| Shock | 16g, 11 ms |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc |
| IECEx | Ex nA IIC T4 Gc |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T4A | |
| Class I, Zone 2, IIC T4 | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |