PHOENIX CONTACT SFP 1-5/120AC SFP 1-5/120AC 2920667 PHOENIX CONTACT EMC filter surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SFP 1-5/120AC 2920667 PHOENIX CONTACT EMC filter surge protection device

SFP 1-5/120AC

2920667

PHOENIX CONTACT

1 Pcs.

EMC filter surge protection device Device protection, according to type 3/class III, with mains parasitic filter against high-frequency edging voltages, for single-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with remote indication contact.

Automation > Surge protection device for terminal equipment
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Combine EMC filtering and fine surge protection in a single DIN-rail module with the Phoenix Contact SFP 1-5/120AC device. These components suppress high-frequency line interference while protecting connected electronic controllers against damaging voltage spikes.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Max. continuous voltage AC (EF004198): 150 V
  • Voltage protection level L-N (EF004236): 0.45 kV
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • With remote signalling contact (EF000422): Yes
  • Signalling at the device (EF004241): Optic
  • Category type 3 (EF004231): Yes
  • Degree of protection (IP) (EF005474): IP20

More info

▲

Key Commercial Data

Orderkey2920667
Packing unit1 pc
Catalog pagePage 185 (C-4-2017)
GTIN4046356158558
Weight per Piece (excluding packing)571.280 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height86.6 mm
Width112 mm
Depth79 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C
Permissible humidity (operation)5 % ... 95 %

General

EN typeT3
Number of portsTwo
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorblack
silver
Housing materialAluminum
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, one-piece
Number of positions2
Surge protection fault messageOptical, remote indicator contact
For country-specific use inUSA, CN, BR

Protective circuit

Nominal voltage UN120 V AC (TN)
120 V AC (TT - only in use with RCD)
120 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC150 V AC
Rated load current IL5 A (70°C)
Residual current IPE≤ 0.6 mA
Nominal discharge current In(8/20) µs3 kA
Standby power consumption PC≤ 7.5 VA (at UREF)
≤ 10 VA (at UC)
Reference test voltage UREF132 V AC
Combination wave UOC6 kV (3 kA)
Voltage protection level Up≤ 0.45 kV
TOV behavior at UT(L-N)175 V AC (5 s / withstand mode)
240 V AC (5 s / safe failure mode)
208 V AC (120 min / safe failure mode)
TOV behavior at UT(L-PE)208 V AC (5 s / withstand mode)
175 V AC (120 min / withstand mode)
1332 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA≤ 25 ns
Capacity (L-N)1 µF ±10 %
10 nF ±10 % (X2-275 V)
Capacity (L-PE)2.2 nF ±20 % (Y2-250 V)
Capacity (L-PEN)2.2 nF ±20 % (Y2-250 V)
Max. required back-up fuse20 A (MCB B/general purpose)
16 A (IT - MCB B/general purpose)
Input attenuation aE, sym.20 dB (≥ 100 kHz / 50 Ω)
Input attenuation aE, asym.30 dB (≥ 1 MHz / 50 Ω)
Short-circuit current rating ISCCR5 kA AC (TN/TT)
1 kA AC (IT)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage12 V AC ... 250 V AC
250 V DC (250 mA DC)
Operating current100 mA AC ... 1 A AC
1 A DC (48 V DC)
Connection methodPluggable screw connection
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG26 ... 16
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm

Connection data

Connection methodScrew terminal blocks
Conductor cross section flexible2.5 mm² ... 4 mm²
Conductor cross section solid2.5 mm² ... 6 mm²
Conductor cross section AWG14 ... 10
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
4.5 lbf-in. ... 5.5 lbf-in.
Stripping length8 mm

UL specifications

SPD Type2CA
Maximum continuous operating voltage MCOV (L-N)150 V AC
Maximum continuous operating voltage MCOV (L-G)150 V AC
Maximum continuous operating voltage MCOV (N-G)150 V AC
Mode of protectionL-N
L-G
N-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Voltage protection rating VPR (L-N)500 V
Voltage protection rating VPR (L-G)500 V
Voltage protection rating VPR (N-G)500 V
Nominal discharge current In3 kA
Short-circuit current rating (SCCR)5 kA

Protective circuit, filter

Discharge resistance820 kΩ

Classifications


Product Datasheet