A Phoenix Contact SFP 1-15/120AC EMC filter surge protection device combines electromagnetic interference filtering with robust surge suppression for sensitive instrumentation and automation electronics. These units ensure clean power delivery and protect critical equipment from high-frequency noise and transient spikes.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Max. continuous voltage AC (EF004198): 150 V
- Voltage protection level L-N (EF004236): 0.45 kV
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- With remote signalling contact (EF000422): Yes
- Signalling at the device (EF004241): Optic
- Category type 3 (EF004231): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2920683 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 185 (C-4-2017) |
| GTIN | 4046356158565 |
| Weight per Piece (excluding packing) | 571.280 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
General
| EN type | T3 |
|---|---|
| Number of ports | Two |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | black |
| silver | |
| Housing material | Aluminum |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, one-piece |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
| For country-specific use in | USA, CN, BR |
Protective circuit
| Nominal voltage UN | 120 V AC (TN) |
|---|---|
| 120 V AC (TT - only in use with RCD) | |
| 120 V AC (IT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 150 V AC |
| Rated load current IL | 15 A (50 °C) |
| Residual current IPE | ≤ 0.6 mA |
| Nominal discharge current In(8/20) µs | 3 kA |
| Standby power consumption PC | ≤ 7.5 VA (at UREF) |
| ≤ 10 VA (at UC) | |
| Reference test voltage UREF | 132 V AC |
| Combination wave UOC | 6 kV (3 kA) |
| Voltage protection level Up | ≤ 0.45 kV |
| TOV behavior at UT(L-N) | 175 V AC (5 s / withstand mode) |
| 240 V AC (5 s / safe failure mode) | |
| 208 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(L-PE) | 208 V AC (5 s / withstand mode) |
| 175 V AC (120 min / withstand mode) | |
| 1332 V AC (200 ms / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Response time tA | ≤ 25 ns |
| Capacity (L-N) | 1 µF ±10 % |
| 10 nF ±10 % (X2-275 V) | |
| Capacity (L-PE) | 2.2 nF ±20 % (Y2-250 V) |
| Capacity (L-PEN) | 2.2 nF ±20 % (Y2-250 V) |
| Max. required back-up fuse | 20 A (MCB B/general purpose) |
| 16 A (IT - MCB B/general purpose) | |
| Input attenuation aE, sym. | 20 dB (≥ 100 kHz / 50 Ω) |
| Input attenuation aE, asym. | 30 dB (≥ 1 MHz / 50 Ω) |
| Short-circuit current rating ISCCR | 5 kA AC (TN/TT) |
| 1 kA AC (IT) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 12 V AC ... 250 V AC |
| 250 V DC (250 mA DC) | |
| Operating current | 100 mA AC ... 1 A AC |
| 1 A DC (48 V DC) | |
| Connection method | Pluggable screw connection |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 16 |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
Connection data
| Connection method | Screw terminal blocks |
|---|---|
| Conductor cross section flexible | 2.5 mm² ... 4 mm² |
| Conductor cross section solid | 2.5 mm² ... 6 mm² |
| Conductor cross section AWG | 14 ... 10 |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| 4.5 lbf-in. ... 5.5 lbf-in. | |
| Stripping length | 8 mm |
UL specifications
| SPD Type | 2CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 150 V AC |
| Maximum continuous operating voltage MCOV (L-G) | 150 V AC |
| Maximum continuous operating voltage MCOV (N-G) | 150 V AC |
| Mode of protection | L-N |
| L-G | |
| N-G | |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Voltage protection rating VPR (L-N) | 500 V |
| Voltage protection rating VPR (L-G) | 500 V |
| Voltage protection rating VPR (N-G) | 500 V |
| Nominal discharge current In | 3 kA |
| Short-circuit current rating (SCCR) | 5 kA |