View larger
CBB 12 2X6RC-PT 2905241 PHOENIX CONTACT Potential distributors
CBB 12 2X6RC-PT
2905241
PHOENIX CONTACT
1 Pcs.
Automation > Fuse terminal block
Over Current Protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
CBB 12 2X6RC-PT is a Phoenix Contact Potential distributors unit designed to simplify complex wiring architectures by cleanly splitting power feeds to multiple outputs. Distribution modules of this type are widely used in control panels to maintain orderly power distribution across automation hardware. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.75 mm²
- Width (EF000008): 232 mm
- Height (EF000040): 127.8 mm
- Depth (EF000049): 70.25 mm
- Closing plate required (EF002525): No
- Colour (EF000007): Grey
More info
▲Key Commercial Data
| Orderkey | 2905241 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 259 (C-6-2015) |
| GTIN | 4046356935371 |
| Weight per Piece (excluding packing) | 584.900 g |
| Custom tariff number | 85363090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -30 °C ... 60 °C (at 48 A, see derating) |
|---|---|
| Ambient temperature (storage/transport) | -30 °C ... 80 °C |
| Humidity test | 96h, 93% RH, 40 °C |
| Degree of protection | IP20 (Terminal blocks and fuse holders) |
| IP00 (PCB) |
General
| Flammability rating according to UL 94 | V0 |
|---|---|
| Mounting type | DIN rail: 35 mm |
| Number of positions | 12 |
| Overvoltage category_GRP | II |
| Protection class | III |
| Degree of pollution | 2 |
| Type | DIN rail module, two-section, divisible |
Electrical data
| Rated voltage main circuit | 24 V DC |
|---|---|
| Rated current main circuit | 60 A DC (total) |
| 12 A DC (per channel) | |
| Rated voltage remote indication circuit | 24 V DC |
| Rated current remote indication circuit | 0.5 A DC |
| Rated surge voltage | 0.5 kV |
| Short circuit stability | 600 A (conditional according to DIN EN 50178) |
| Power dissipation | 4.5 W (without circuit breaker) |
| Insertion/withdrawal cycles | 50 |
Connection data
| Connection name | Supply X21 |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 18 mm |
| Conductor cross section solid | 0.75 mm² ... 16 mm² |
| Conductor cross section AWG | 20 ... 4 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.75 mm² ... 10 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.75 mm² ... 16 mm² |
| Connection name | Outputs X1 ... X12 |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
| Connection name | Remote signaling X31 |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Standards and Regulations
| Standards/specifications | DIN EN 50178 1997 |
|---|---|
| DIN EN 61000-6-2:2005 | |
| DIN EN 61000-6-3:2007+A1:2011 | |
| DIN EN 60068-2-6 |