View larger
CBB TM 08 2X4RC P-PT 2801482 PHOENIX CONTACT Potential distributors
CBB TM 08 2X4RC P-PT
2801482
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for low-voltage switch technology
Over Current Protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact potential distributor serves as a centralized terminal block designed to branch a single power or signal input into multiple discrete distribution paths within control cabinets. Panel builders utilize these distribution modules to organize common supply lines cleanly without cluttering terminal strips. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): Yes
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 2801482 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 262 (C-6-2013) |
| GTIN | 4046356782326 |
| Weight per Piece (excluding packing) | 557.000 g |
| Custom tariff number | 85362010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -30 °C ... 60 °C (at In 60 A) |
|---|---|
| Ambient temperature (storage/transport) | -30 °C ... 80 °C |
| Degree of protection | IP20 (Terminal blocks and fuse holders) |
| IP00 (PCB) |
General
| Flammability rating according to UL 94 | V0 |
|---|---|
| Mounting type | DIN rail: 35 mm |
| Number of positions | 8 |
| Overvoltage category_GRP | II |
| Protection class | III |
| Degree of pollution | 2 |
| Type | DIN rail module, two-section, divisible |
Electrical data
| Rated voltage main circuit | 24 V DC |
|---|---|
| Rated current main circuit | 60 A DC (total) |
| 12 A DC (per channel) | |
| Rated voltage remote indication circuit | 24 V DC |
| Rated current remote indication circuit | 1 A DC |
| Rated insulation voltage Ui | 50 V DC |
| Rated surge voltage | 0.5 kV |
| Short circuit stability | 600 A (conditional according to DIN EN 50178) |
| Power dissipation | 4.9 W (with even load on outputs with In) |
| Insertion/withdrawal cycles | 50 |
Connection data
| Connection name | Supply X21 |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 18 mm |
| Conductor cross section flexible min. | 0.75 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section solid min. | 0.75 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 4 |
| Connection name | Outputs X1 ... X8 |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Connection name | Remote signaling X31 |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |