This solid-state relay terminal block, part number DEK-OE-24DC/ 48DC/100/T by Phoenix Contact, integrates switching and terminal block functions into a single space-saving modular housing. Terminal block relays are widely applied in industrial environments for bridging control systems and actuators with efficient optical isolation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 21.6 V
- Type of voltage (input voltage) (EF003033): DC
- Output voltage (EF003933): 3 V
- Type of output voltage (EF008222): DC
- Rated operation current Ie (EF001443): 0.1 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 2964254 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 71 (IF-2002) |
| GTIN | 4017918100803 |
| Weight per Piece (excluding packing) | 21.060 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.9 ... 1.1 |
| Input voltage range | 21.6 V DC ... 26.4 V DC |
| Switching threshold "0" signal in reference to UN | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |
| Typical input current at UN | 6.5 mA |
| Typical response time | 40 µs (delay) |
| Typical turn-off time | 40 µs (delay) |
| Status display | Yellow LED |
| Type of protection | Reverse polarity protection |
| Protective circuit/component | Bridge rectifier |
| Transmission frequency | 30 Hz |
Output data
| Output voltage range | 3 V DC ... 48 V DC |
|---|---|
| Limiting continuous current | 100 mA |
| Voltage drop at max. limiting continuous current | ≤ 0.9 V |
| Output circuit | 2-wire, floating |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Protective circuit/component | Polarity protection diode |
Connection data, input side
| Connection name | Input side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Connection data, output side
| Connection name | Output side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
General
| Note | The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949). |
|---|---|
| Type of note | Note on application |
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Test voltage input/output | 2.5 kV AC |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
| Standards/regulations | IEC 60664 |
| IEC 60664A | |
| DIN VDE 0110 | |
| Degree of pollution | 2 |
| Overvoltage category | III |
Standards and Regulations
| Standards/regulations | IEC 60664 |
|---|---|
| IEC 60664A | |
| DIN VDE 0110 | |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |