Phoenix Contact D-LAN-CAT.5-HC surge protection device is designed to secure high-speed data networks and Ethernet communication hardware against damaging transient voltage surges. It integrates smoothly into structured cabling architectures to protect expensive active network components. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2800763
- Packing unit: 1 pc
- GTIN: 4046356730280
- Weight per Piece (excluding packing): 25.000 g
- Custom tariff number: 85363030
- Country of origin: CN (China)
- Height: 110 mm
- Width: 28 mm
- Depth: 60 mm (incl. NS 35 adapter)
- Ambient temperature (operation): -40 °C ... 85 °C
- Degree of protection: IP20
- Housing material: PC+ABS
- Flammability rating according to UL 94: V-0
- Color: gray
- Standards for cearances and creepage distances: VDE 0110-1
- Mounting type: Connection-specific attachment plug and DIN rail, 35 mm
More info
▲Key Commercial Data
| Orderkey | 2800763 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4046356730280 |
| Weight per Piece (excluding packing) | 25.000 g |
| Custom tariff number | 85363030 |
| Country of origin | CN (China) |
General
| Housing material | PC+ABS |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | gray |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664 | |
| Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
| Type | Attachment plug for DIN rail mounting |
| Number of positions | 8 |
| Direction of action | Line-Line & Line-Ground/Shield |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C2 | |
| D1 | |
| VDE requirement class | B2 |
| C2 | |
| D1 | |
| Maximum continuous voltage UC | ± 5 V DC |
| Maximum continuous voltage UC(wire-wire) | ± 5 V DC (± 57 V DC / PoE+) |
| Nominal current IN | ≤ 1.5 A (25 °C) |
| Operating effective current ICat UC | ≤ 600 µA |
| Nominal discharge current In(8/20) µs (line-line) | 350 A |
| 350 A (per signal pair) | |
| Nominal discharge current In(8/20) µs (line-earth) | 2 kA (per signal pair) |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 1 kA (per signal pair) |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (per signal pair) |
| Nominal pulse current Ian (10/700) µs (line-line) | ≤ 25 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | ≤ 100 A |
| Nominal pulse current Ian (10/700) µs (line-line) | ≤ 25 A (per signal pair) |
| Nominal pulse current Ian (10/700) µs (line-earth) | ≤ 100 A (per signal pair) |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 25 V |
| ≤ 90 V (PoE) | |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 750 V |
| Residual voltage at In(line-line) | ≤ 35 V |
| ≤ 110 V (PoE) | |
| Residual voltage at In(line-earth) | ≤ 850 V (per signal pair) |
| Voltage protection level Up(line-line) | ≤ 20 V (B2 - 1 kV / 25 A) |
| ≤ 90 V (B2 - 1 kV / 25 A - PoE) | |
| ≤ 35 V (700 V / 350 A) | |
| ≤ 110 V (700 V / 350 A - PoE) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (B2 - 4 kV / 100 A) |
| ≤ 850 V (C2 - 4 kV / 2 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | ≤ 0.5 dB (100 MHz/100 Ω) |
| ≤ 1 dB (100 MHz/100 Ω/Link Class E) | |
| Near-end crosstalk attenuation | typ. 63 dB (1 MHz/100 Ω/Link Class E) |
| typ. 43 dB (16 MHz / 100 Ω / Link Class E) | |
| typ. 30 dB (100 MHz/100 Ω/Link Class E) | |
| > 40 dB (100 MHz/100 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | > 100 MHz |
| Capacity (line-line) | typ. 15 pF (f= 1 MHz / VR= 0 V) |
| Capacity (line-earth) | typ. 5 pF (f= 1 MHz / VR= 0 V) |
| Impulse durability (line-line) | B2 - 1 kV / 25 A |
| Impulse durability (line-earth) | B2 - 4 kV / 100 A |
| C2 - 4 kV/2 kA | |
| D1 - 1kA |
Standards and Regulations
| Standards/specifications | IEC 61643-21/A1 2008 |
|---|---|
| GB/T 18802.21 2004 | |
| EN 61643-21/A1 2009 | |
| IEC 61643-21 2000 |