View larger
PSR-PS21-1NO-1NC-24DC-SC 2700357 PHOENIX CONTACT Coupling relay
PSR-PS21-1NO-1NC-24DC-SC
2700357
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
PSR-PS21-1NO-1NC-24DC-SC 2700357 PHOENIX CONTACT Coupling relay serves as a vital interposing module that bridges control units and higher-load actuators while maintaining strict electrical isolation. Engineers use these components to adapt signal voltages, protect controllers from feedback transients, and ensure reliable electrical switching. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Basic device
- Suitable for rail mounting (EF003972): Yes
- With detachable clamps (EF003340): No
- Type of electric connection (EF003961): Screw connection
- Suitable for monitoring of valves (EF007272): No
- Suitable for monitoring of tactile sensors (EF007271): No
- Suitable for monitoring of magnetic switches (EF007266): No
- Suitable for monitoring of proximity switches (EF007267): No
- With start input (EF003342): No
- With muting function (EF004057): No
- With feedback circuit (EF003343): No
- Release-delay (EF001129): 0.1 s
- With approval for BG BIA (EF004145): No
- With approval according to UL (EF001783): No
- Width (EF000008): 6.8 mm
- Height (EF000040): 93.1 mm
More info
▲Key Commercial Data
| Orderkey | 2700357 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 281 (C-6-2017) |
| GTIN | 4046356912907 |
| Weight per Piece (excluding packing) | 136.400 g |
| Custom tariff number | 85364900 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 65 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Power supply
| Rated control circuit supply voltage US | 24 V DC -15 % / +10 % (A1/A2) |
|---|---|
| 20.4 V DC ... 26.4 V DC | |
| Rated control supply current IS | typ. 45 mA |
| Power consumption at US | typ. 1.08 W |
| Inrush current | typ. 400 mA (Δt s) |
| Filter time | max. 2 ms (at A1-A2; test pulse width) |
| ≥ 100 ms (at A1-A2; test pulse rate) | |
| Diagnostic supply voltage UD | 24 V DC -15 % / +10 % (21/A2) |
| Input current at UD | 6 mA (at 21-A2 for UD; depending on load + 100 mA at M1 and 22) |
| Inrush current at UD | typ. 2.5 A (Δt D) |
| Protective circuit | Serial protection against polarity reversal Suppressor diode 33 V (A1/A2), 38 V (21/A2) |
Relay outputs: enabling current path
| Output name | Enabling current path |
|---|---|
| Output description | 1 N/O contact, without delay, floating |
| Number of outputs | 1 (safety-related N/O contacts: 13/14) |
| Contact type | 1 enabling current path |
| Contact material | AgSnO2 |
| Switching voltage | min. 12 V AC/DC |
| max. 250 V AC/DC (Observe the load curve) | |
| Limiting continuous current | 6 A (High demand) |
| 4 A (Low demand) | |
| Inrush current | min. 3 mA |
| max. 6 A | |
| Sq. Total current | 36 A2(observe derating) |
| Switching capacity | min. 60 mW |
| Switching frequency | max. 1 Hz |
| Mechanical service life | 10x 106cycles |
| Switching capacity according to IEC 60947-5-1 | 4 A (24 V (DC13)) |
| 5 A (250 V (AC15)) | |
| Output fuse | 6 A gL/gG |
| 4 A gL/gG (for low-demand applications) |
Relay outputs: return current/signaling current path
| Output name | Confirmation current path |
|---|---|
| Output description | 1 N/C contact, without delay, not floating (reference ground: A2) |
| Number of outputs | 1 (safety-related N/C contacts: 21/22) |
| Contact type | 1 confirmation current path |
| Contact material | AgCuNi, + Au |
| Switching voltage | min. 20.4 V DC |
| max. 26.4 V DC | |
| Limiting continuous current | 100 mA |
| Inrush current | min. 1 mA |
| max. 100 mA | |
| Switching capacity | min. 20 mW |
| Switching frequency | max. 1 Hz |
| Mechanical service life | 10x 106cycles |
| Output fuse | 150 mA Fast-blow |
Alarm outputs
| Output description | PNP |
|---|---|
| Number of outputs | 1 (non-safety-related) |
| Voltage | approx. 22 V DC (UD- 2 V) |
| Current | max. 100 mA |
| Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
| Short-circuit protection | no |
| Output fuse | 150 mA fast blow |
Times
| Typical pickup time at US | < 100 ms (with Uswhen controlled via A1) |
|---|---|
| Typical release time at US | < 35 ms (when controlled via A1) |
| Recovery time | 500 ms |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 136.4 g |
| Mounting position | vertical, horizontal, with front of module upward |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |
| Operating voltage display | 1 x yellow LED |
| Status display | 2 x green LEDs |
| Indication | 1 x red LED |
Connection data
| Connection method | Screw connection |
|---|---|
| pluggable | no |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 12 mm |
| Screw thread | M3 |
| Torque | 0.5 Nm ... 0.6 Nm |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 2 |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 2 |
| Designation | EN 50156 |
| Safety Integrity Level (SIL) | 2 |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178, EN 60079-15 |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, confirmation current path, signal output to the enabling current path; 4 kV/basic insulation between all current paths and housing |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g |
| Vibration (operation) | 10 Hz ...150 Hz, 2g |
| Conformance | CE-compliant |
| UL, USA/Canada | cULus |
| Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X | |
| Class I, Div. 2, Groups A, B, C, D, T4 | |
| GL | C, EMC2 |
| Environmental simulation test | ISA-S71.04 (G3) |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |