View larger
QUINT-PS- 24DC/24DC/10 2866378 PHOENIX CONTACT DC/DC converters
QUINT-PS-24DC/24DC/10
2866378
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact QUINT-PS-24DC/24DC/10 DC/DC converter is utilized in industrial applications to regulate, stabilize, and isolate direct current voltages. These converter modules eliminate line disturbances and maintain precise voltage parameters for sensitive automation hardware. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2866378
- Packing unit: 1 pc
- Catalog page: Page 598 (IF-2009)
- GTIN: 4017918987169
- Weight per Piece (excluding packing): 1,364.300 g
- Custom tariff number: 85044030
- Country of origin: CN (China)
- Width: 80 mm
- Height: 130 mm
- Depth: 125 mm
- Width with alternative assembly: 122 mm
- Height with alternative assembly: 130 mm
- Depth with alternative assembly: 83 mm
- Degree of protection: IP20
- Ambient temperature (operation): -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Ambient temperature (storage/transport): -40 °C ... 85 °C
More info
▲Key Commercial Data
| Orderkey | 2866378 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 598 (IF-2009) |
| GTIN | 4017918987169 |
| Weight per Piece (excluding packing) | 1,364.300 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
Dimensions
| Width | 80 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 83 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage | 24 V DC |
|---|---|
| Nominal input voltage range | 24 V DC |
| Input voltage range | 18 V DC ... 32 V DC |
| Frequency range DC | 0 Hz |
| Current consumption | typ. 11.4 A (24 V) |
| Inrush surge current | < 20 A (typical) |
| Mains buffering | > 3 ms (24 V DC) |
| Input fuse | 25 A (slow-blow, internal) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 22.5 V DC ... 28.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | 35 V DC |
| Output overvoltage protection | < 35 V DC |
| Max. capacitive load | unlimited |
| Active current limitation | Approx. 18 A |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 2 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 60 mVPP |
| Output power | 240 W |
| Typical response time | < 1 s |
| Maximum power dissipation in no-load condition | < 2 W |
| Power loss nominal load max. | < 28 W |
General
| Net weight | 0.95 kg |
|---|---|
| Operating voltage display | Green LED |
| Efficiency | > 88 % |
| Insulation voltage input/output | 1 kV (routine test) |
| 1.5 kV (type test) | |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 500000 h |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Connection data, input
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Signaling
| Output name | DC OK active |
|---|---|
| Output description | UOUT> 21.5 V: High signal |
| Maximum switching voltage | ≤ 24 V DC |
| Output voltage | + 24 V DC |
| Continuous load current | ≤ 40 mA |
| Status display | "DC OK" LED green |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Screw thread | M3 |
| Output name | DC OK floating |
| Output description | UOUT> 21.5 V: Contact closed |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Continuous load current | ≤ 1 A |
| Status display | "DC OK" LED green |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive 89/336/EC |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 8 kV |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 2 GHz |
| Test field strength | 10 V/m |
| Standards/regulations | EN 61000-4-4 |
| EN 61000-6-3 | |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V |
| Standards/regulations | EN 61000-4-11 |
| Standard - Safety of transformers | EN 61558-2-17 |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| EN 60204 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| Shipbuilding approval | DNV GL (EMC A), ABS |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |