View larger
PSR-SPP- 24DC/URM4/4X1/2X2/B 2981680 PHOENIX CONTACT Extension module
PSR-SPP-24DC/URM4/4X1/2X2/B
2981680
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact extension module PSR-SPP-24DC/URM4/4X1/2X2/B (part number 2981680) is an expansion device utilized in industrial safety circuits to multiply available contact paths and safely expand control system capabilities. Units of this type integrate into machine safety setups to monitor various interlocking and switching elements. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Expansion device
- Suitable for rail mounting (EF003972): Yes
- With detachable clamps (EF003340): Yes
- Type of electric connection (EF003961): Spring clamp connection
- Suitable for monitoring of valves (EF007272): No
- Suitable for monitoring of tactile sensors (EF007271): No
- Suitable for monitoring of magnetic switches (EF007266): No
- Suitable for monitoring of proximity switches (EF007267): No
- With muting function (EF004057): No
- With feedback circuit (EF003343): No
- Release-delay (EF001129): 0.01 s
- With approval for BG BIA (EF004145): No
- With approval according to UL (EF001783): No
- Width (EF000008): 22.5 mm
- Height (EF000040): 112 mm
- Depth (EF000049): 114.5 mm
More info
▲Key Commercial Data
| Orderkey | 2981680 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 265 (C-6-2017) |
| GTIN | 4046356081542 |
| Weight per Piece (excluding packing) | 196.500 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | max. 2000 m (Above sea level) |
Input data
| Rated control circuit supply voltage US | |
|---|---|
| Nominal input voltage UN | 24 V DC |
| Input voltage range in reference to UN | 0.9 ... 1.1 |
| Typical input current at UN | 42 mA |
| Typical response time | 10 ms |
| Typical release time | 10 ms |
| Recovery time | 1 s |
| Status display | Green LED |
| Protective circuit | Surge protection Suppressor diode |
Output data
| Contact type | 4 enabling current paths |
|---|---|
| 1 signaling current path | |
| 1 confirmation current path | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 15 V AC/DC |
| Limiting continuous current | 6 A (N/O contact, DC1/AC1) |
| 3 A (N/C contact) | |
| Maximum inrush current | 6 A (N/O contact, DC1/AC1) |
| 3 A (N/C contact) | |
| Inrush current, minimum | 25 mA |
| Sq. Total current | 72 A2(ITH2= I12+ I22+ I32+ I42) |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms, N/C contact 61/62: 72 W) |
| 288 W (48 V DC, τ = 0 ms, N/C contact 61/62: 144 W) | |
| 77 W (110 V DC, τ = 0 ms) | |
| 88 W (220 V DC, τ = 0 ms) | |
| 1500 VA (250 V AC, τ = 0 ms, N/C contact 61/62: 750 VA) | |
| Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
| 40 W (48 V DC, τ = 40 ms) | |
| 35 W (110 V DC, τ = 40 ms) | |
| 33 W (220 V DC, τ = 40 ms) | |
| Switching capacity min. | 0.4 W |
| Mechanical service life | approx. 107cycles |
| Switching capacity (360/h cycles) | 6 A (24 V DC) |
| 5 A (230 V AC) | |
| Switching capacity according to IEC 60947-5-1 | 5 A (DC13) |
| 5 A (AC15) | |
| Output fuse | 10 A gL/gG NEOZED (N/O contact) |
| 4 A gL/gG NEOZED (N/C contact) |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 196.5 g |
| Mounting position | any |
| Mounting type | DIN rail mounting |
| Degree of protection | IP20 |
| IP54 | |
| Min. degree of protection of inst. location | IP54 |
| Housing color | yellow |
Connection data
| Connection method | Spring-cage connection |
|---|---|
| pluggable | Yes |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Designation | EN ISO 13849 |
| Performance level (PL) | e (In conjunction with suitable evaluating device) |
| Category | 4 (In conjunction with suitable evaluating device) |
| Designation | EN 62061 |
| Safety Integrity Level Claim Limit (SIL CL) | 3 (In conjunction with suitable evaluating device) |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | IEC 60947-1 |
| Rated insulation voltage | 250 V |
| Rated surge voltage/insulation | 4 kV / basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit/N/C contacts and enabling current paths). |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |