A Phoenix Contact MINI MCR-TC-UI-NC thermocouple measuring transducer is a signal conditioning device used to convert temperature signals from thermocouples into standardized analog process signals. These transducers are commonly integrated into industrial control panels to safely isolate, filter, and transmit sensor data to programmable logic controllers and monitoring systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Measuring range (EF001836): -250 °C
- Analogue output 0 mA ... 20 mA (EF006808): No
- Analogue output 4 mA ... 20 mA (EF006810): No
- Analogue output 0 V ... 2 V (EF009886): No
- Analogue output 0 V ... 5 V (EF009887): Yes
- Analogue output 0 V ... 10 V (EF006807): Yes
- Analogue output 2 V ... 10 V (EF009888): No
- With switching output (EF005225): No
- Modular version (EF001126): Yes
- Integrated configuration function (EF003064): Yes
- EMC-version (EF001062): Yes
- Ambient temperature (EF002386): 65 °C
- Weight (EF000167): 0.1178 kg
More info
▲Key Commercial Data
| Orderkey | 2902851 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 107 (C-7-2015) |
| GTIN | 4046356689229 |
| Weight per Piece (excluding packing) | 118.400 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Input data
| Configurable/programmable | Yes |
|---|---|
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L |
| Temperature measuring range | -250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches) |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Voltage output signal | 0 V ... 10 V |
| 10 V ... 0 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| 20 mA ... 0 mA | |
| 20 mA ... 4 mA | |
| Max. output voltage | approx. 12.3 V |
| Max. output current | 24.6 mA |
| Short-circuit current | < 31.5 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | < 500 Ω (at 20 mA) |
| Ripple | < 20 mVPP |
| < 20 mVPP(at 500 Ω) |
Power supply
| Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
|---|---|
| Max. current consumption | 72 mA |
| Typical current consumption | < 27 mA (at 24 V DC) |
| Power consumption | ≤ 700 mW (at IOUT= 20 mA, 9.6 V DC, load 500 Ω) |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 12 mm |
| Screw thread | M3 |
General
| Transmission error thermocouples | 0.1 % * 600 K / set measuring range; 0.1 % > 600 K (E, J, K, N, T, L, U, M Gost, L Gost) |
|---|---|
| 0.2 % * 600 K / set measuring range; 0.2 % > 600 K (B, R, S, A1, A2, A3) | |
| 0.2% * 600 K / set measuring range; 0.2% > 600 K (E, J, K, N, T, L, U, M Gost, L Gost); Highspeed Mode | |
| 0.4% * 600 K / set measuring range; 0.4% > 600 K (B, R, S, A1, A2, A3); Highspeed Mode | |
| Maximum temperature coefficient | ≤ 0.01 %/K |
| Cold point error, max. | < 3 K |
| Typical cold point errors | < 2 K |
| Status display | LED red |
| Protective circuit | Transient protection |
| Electrical isolation | Basic insulation according to EN 61010 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 50 V AC/DC |
| Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | PBT |
| Mounting position | any |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC | |
| Certificate of classification | DNV GL 14085-15HH |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Basic insulation according to EN 61010 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|