PHOENIX CONTACT CB E1 24DC/4A S-R P CB E1 24DC/4A S-R P 2800911 PHOENIX CONTACT Electronic device circuit breaker View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CB E1 24DC/4A S-R P 2800911 PHOENIX CONTACT Electronic device circuit breaker

CB E1 24DC/4A S-R P

2800911

PHOENIX CONTACT

1 Pcs.

Electronic device circuit breaker Interruption. Protec. Electronic, 1-pole, active current limiter, status output and reset input, connector for base element. Electronic circuit breaker, 1-pos., active current limitation, status output and reset input, plug for base element.

Automation > Device circuit breaker
Over Current Protection

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An electronic device circuit breaker like the Phoenix Contact CB E1 24DC/4A S-R P provides precision overcurrent protection and active current limitation for 24 V DC industrial control loops. These modular units ensure that localized electrical faults are isolated immediately without compromising the broader automation network. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Device circuit breakers
  • Product family: CB E
  • Type: Male
  • Number of positions: 1
  • No. of channels: 1
  • Data management status Article revision: 03
  • Insulation characteristics Degree of pollution: 2
  • General Operating voltage: 24 V DC
  • Nominal current I N: 4 A
  • Rated surge voltage: 0.5 kV
  • Tripping method: E (electronic)
  • Required backup fuse: not required, integrated failsafe element
  • Dielectric strength: max. 30 V DC (Load circuit)
  • Active current limitation: typ. 1.25 x I N
  • Fuse: electronic
  • Closed circuit current I 0: typ. 8 mA (When switched on)

More info

▲
Technical data

Notes
GeneralWhen mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).
Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).
Parallel connection of multiple circuit breakers is not permitted.

Product properties
Product typeDevice circuit breakers
Product familyCB E
TypeMale
Number of positions1
No. of channels1
Data management status
Article revision03
Insulation characteristics
Degree of pollution2

Electrical properties
General
Operating voltage24 V DC
18 V DC ... 30 V DC
Nominal current IN4 A
Rated surge voltage0.5 kV
Tripping methodE (electronic)
Required backup fusenot required, integrated failsafe element
Dielectric strengthmax. 30 V DC (Load circuit)
Active current limitationtyp. 1.25 x IN
Fuseelectronic
Closed circuit current I0typ. 8 mA (When switched on)
typ. 11 mA (With status output)
Power dissipation0.66 W (Nominal operation)
Temperature derating4 A (at 50 °C)
MTBF (IEC 61709, SN 29500)8320000 h (at 25 °C with 80 % load)
7410000 h (at 40 °C with 80 % load)
Voltage drop100 mV (at IN)
Fail-safe element6 A DC
Load circuit
Shutdown time200 ms (see time/current characteristic curve)
Undervoltage switch-off< 14 V (typ. OFF)
> 17 V (typ. ON)
Max. capacitive load20000 µF
Switch-on delaytyp. 2 ms
Auxiliary contact
Contact connection typePositive-switching signal output
Reset
Input voltage range7 V DC ... 30 V DC (Reset with falling edge)
Current consumptiontyp. 2.6 mA (at 24 V DC)
Pulse lengthmin. 20 ms
Voltage< 3 V DC (Low state)
> 8 V DC (High state)
Status output
Output voltage24 V DC
Output currentmax. 0.2 A (Short-circuit-proof)

Connection data
Connection methodpluggable

Dimensions
Dimensional drawing
Width12.3 mm
Height45 mm
Depth52 mm
Complete module width12.3 mm
Complete module height90 mm
Complete module depth77.3 mm

Material specifications
Colorgray (RAL 7042)
black (RAL 9005)
Flammability rating according to UL 94V-0

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP30 (Actuation area)
Ambient temperature (operation)-25 °C ... 50 °C (non-condensing)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Humidity test96 h, 95 % RH, 40 °C
Vibration (operation)3g (according to IEC 60068-2-6, Test Fc)

Approvals
UL approval
IdentificationUL Listed UL 508
UL Recognized UL 2367
Shipbuilding approval
IdentificationDNV GL

Standards and regulations
Standard designationEMV
Standards/specificationsEN 61000-6-3
NoteInterference emission
Standard designationEMV
Standards/specificationsEN 61000-6-2
NoteNoise immunity

Mounting
Mounting typeon base element

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.