View larger
SAC-4P-10,0-28X/M12FS SH OD 1454176 PHOENIX CONTACT Sensor/actuator cable
SAC-4P-10,0-28X/M12FS SH OD
1454176
PHOENIX CONTACT
1 Pcs.
Automation > Sensor-actuator patch cord
Industrial Field Connectivity (IFC)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The SAC-4P-10,0-28X/M12FS SH OD 1454176 PHOENIX CONTACT Sensor/actuator cable serves as an integral pathway for signal distribution throughout industrial plants. These factory-terminated configurations maintain signal integrity and environmental protection for heavy machinery operations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Type of electrical connection, box-sided (EF005524): M12
- Type of plug-in contact, box-sided (EF008386): Female (bus)
- Positioning cable feed, box-sided (EF005927): Straight
- Cable length (EF000536): 10 m
- Halogen free (EF000025): Yes
- With LED indication (EF005950): No
- Screened (EF000881): Yes
- Cable type (EF000081): Multi-core
- Vulcanize (EF004115): Yes
- Material contact body (EF008248): CuSn
- Rated current In (EF008250): 4 A
- Rated voltage (EF000228): 48 V
- Degree of protection (IP) (EF005474): IP65
More info
▲Key Commercial Data
| Orderkey | 1454176 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 154 (C-4-2013) |
| GTIN | 4046356568784 |
| Weight per Piece (excluding packing) | 729.400 g |
| Custom tariff number | 85444290 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 105 °C (Plug / socket) |
|---|---|
| -40 °C ... 85 °C (On sudden changes in temperature (according to IEC 60512-11-4)) | |
| Degree of protection | IP65 |
| IP67 | |
| IP68 | |
| IP69K |
General
| Rated current at 40°C | 4 A |
|---|---|
| Rated voltage | 48 V AC |
| 60 V DC | |
| Number of positions | 4 |
| Insulation resistance | ≥ 100 MΩ |
| Coding | A - standard |
| Standards/regulations | M12 connector IEC 61076-2-101 |
| Status display | No |
| Protective circuit/component | unwired |
| Degree of pollution | 3 |
| Insertion/withdrawal cycles | ≥ 100 |
| Torque | 0.4 Nm (M12 connector) |
Material
| Flammability rating according to UL 94 | V0 |
|---|---|
| Contact material | CuSn |
| Contact surface material | Ni/Au |
| Contact carrier material | PP |
| Material of grip body | PP |
| Material, knurls | Stainless steel |
| Sealing material | FPM |
Standards and Regulations
| Standard designation | M12 connector |
|---|---|
| Standards/regulations | IEC 61076-2-101 |
| Flammability rating according to UL 94 | V0 |
Cable
| Cable type | PE-X black |
|---|---|
| Cable type (abbreviation) | 28X |
| Cable abbreviation | Li2X2X-C-Vl-2X |
| Conductor cross section | 4x 0.5 mm² (Signal line) |
| AWG signal line | 20 |
| Conductor structure signal line | 28x 0.15 mm |
| Core diameter including insulation | 1.6 mm ±0.05 mm (Signal line) |
| Thickness, insulation | approx. 0.3 mm (Core insulation) |
| approx. 0.7 mm (Outer cable sheath) | |
| approx. 0.45 mm (Inner sheath) | |
| Wire colors | brown, white, blue, black |
| Overall twist | 4 wires, twisted |
| Length of twist, overall twist | 108.8 mm |
| Shielding | Braided copper wires |
| Optical shield covering | 85 % |
| External sheath, color | black-gray RAL 7021 |
| External cable diameter D | 6.8 mm ±0.2 mm |
| Smallest bending radius, fixed installation | 34 mm |
| Smallest bending radius, movable installation | 68 mm |
| Number of bending cycles | 1000000 |
| Bending radius | 68 mm |
| Traversing path | 10 m |
| Traversing rate | 3 m/s |
| Acceleration | 10 m/s² |
| Cable weight | 74 kg/km |
| Outer sheath, material | PE-X |
| Material, inner sheath | PE-X |
| Material conductor insulation | PE-X |
| Conductor material | Bare Cu litz wires |
| Insulation resistance | ≥ 100 MΩ*km (at 20 °C) |
| Conductor resistance | ≤ 39 Ω/km (at 20 °C) |
| Cable capacity | ≤ 100 nF/km (Conductor-conductor, asymmetrical/touching) |
| ≤ 85 nF/km (Conductor-conductor, symmetrical/star quad) | |
| ≤ 150 nF/km (Wire/shield) | |
| Conductor inductance | 0.64 mH/km (at 1 kHz) |
| 0.46 mH/km (at 10 MHz) | |
| Nominal voltage, cable | ≤ 300 V AC |
| Test voltage, cable | ≥ 3000 V AC |
| Special properties | Irradiated |
| Flame resistance | according to DIN 60332-1-2 |
| according to DIN EN 50266-2-5 | |
| Halogen-free | in accordance with DIN VDE 0472 part 815 |
| Resistance to oil | in accordance with DIN EN 60811-2-1 |
| Other resistance | UV resistant according to DIN VDE 0276-605 |
| Ambient temperature (operation) | -40 °C ... 105 °C (cable, fixed installation) |
| -15 °C ... 105 °C (cable, flexible installation) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |