Phoenix Contact sensor/actuator cable (part number SAC-12P- 1,0-35T/FS SH SCO) connects complex multi-pin measurement devices and control units in high-density automated systems. Multi-core shielded assemblies maintain signal clarity when operating near electromagnetic interference. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 12
- Type of electrical connection, box-sided (EF005524): M12
- Type of plug-in contact, box-sided (EF008386): Female (bus)
- Positioning cable feed, box-sided (EF005927): Straight
- Cable length (EF000536): 1 m
- Halogen free (EF000025): Yes
- With LED indication (EF005950): No
- Screened (EF000881): Yes
- Cable type (EF000081): Multi-core
- Vulcanize (EF004115): No
- Material contact body (EF008248): CuZn
- Rated current In (EF008250): 1.5 A
- Rated voltage (EF000228): 30 V
- Degree of protection (IP) (EF005474): IP65
More info
▲Key Commercial Data
| Orderkey | 1434730 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 220 (C-2-2017) |
| GTIN | 4046356456692 |
| Weight per Piece (excluding packing) | 114.100 g |
| Custom tariff number | 85444290 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 85 °C (Plug / socket) |
|---|---|
| Degree of protection | IP65 |
| IP67 |
General
| Rated current at 40°C | 1.5 A |
|---|---|
| Rated voltage | 30 V AC |
| 30 V DC | |
| Number of positions | 12 |
| Insulation resistance | ≥ 100 MΩ |
| Coding | A - standard |
| Standards/regulations | M12 connector IEC 61076-2-101 |
| Status display | No |
| Protective circuit/component | unwired |
| Overvoltage category | II |
| Degree of pollution | 3 |
| Torque | 0.4 Nm (M12 connector) |
Material
| Flammability rating according to UL 94 | V0 |
|---|---|
| Contact material | CuZn |
| Contact surface material | Ni/Au |
| Contact carrier material | PA 6.6 |
| Material of grip body | TPU, hardly inflammable, self-extinguishing |
| Material, knurls | Zinc die-cast, nickel-plated |
| Sealing material | NBR |
Cable
| Cable type | Black PUR/PVC twisted pair |
|---|---|
| Cable type (abbreviation) | 35T |
| Conductor cross section | 0.14 mm² |
| AWG signal line | 26 |
| Conductor structure signal line | 18x 0.10 mm |
| Core diameter including insulation | 1 mm ±0.05 mm |
| Wire colors | White-brown, green-yellow, gray-pink, blue-red, black-violet, gray/pink-red/blue |
| Overall twist | Six pairs around the filler to the core |
| Shielding | Tinned copper braided shield |
| Optical shield covering | 85 % |
| External sheath, color | black RAL 9005 |
| External cable diameter | 8.50 mm |
| Number of bending cycles | 2000000 |
| Bending radius | 85 mm |
| Traversing path | 10 m |
| Traversing rate | 3 m/s |
| Acceleration | 10 m/s² |
| Outer sheath, material | PUR |
| Material conductor insulation | PVC |
| Conductor material | Tin-plated Cu litz wires |
| Standards/specifications | M12 connector IEC 61076-2-101 |
| Conductor resistance | 142 Ω/km |
| Flame resistance | DIN VDE 0472 part 804, test type B |
| Resistance to oil | DIN VDE 0472 Part 803, test type B |
| Other resistance | Hydrolysis and microbe resistant as per VDE 0282 section 10 |
| Ambient temperature (operation) | -40 °C ... 80 °C (cable, fixed installation) |
| -5 °C ... 80 °C (cable, flexible installation) |
Standards and Regulations
| Standard designation | M12 connector |
|---|---|
| Standards/regulations | IEC 61076-2-101 |
| Flame resistance | DIN VDE 0472 part 804, test type B |
| Resistance to oil | DIN VDE 0472 Part 803, test type B |
| Other resistance | Hydrolysis and microbe resistant as per VDE 0282 section 10 |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |