Request QuoteProduct Overview
Phoenix Contact system cable CABLE-D25/B/FLK16/10,0M/AI845 links control hardware and analog or digital input units within automated industrial systems. Prefabricated assemblies ensure secure signal transmission and reduce installation time in complex panel builds. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: System cable
- Data management status Article revision: 03
- Ambient conditions Degree of protection: IP00
- Degree of protection (Installation location): ≥ IP54 (Installation location)
- Ambient temperature (operation): -40 °C ... 70 °C (fixed installation)
- Ambient temperature (storage/transport): -20 °C ... 70 °C
- Altitude: ≤ 2000 m
- Operating voltage (AC): ≤ 30 V AC
- Operating voltage (DC): ≤ 60 V DC
- Nominal operating mode: 100% operating factor
- Current (Per path, 50°C): ≤ 1 A (Uncoiled, see derating)
- Current (Per path, 70°C): ≤ 0.6 A (Uncoiled, see derating)
- Cable length: 10 m
- 16X0.14 [PVC] Number of positions: 16
- Shielded: yes
- Cable type: 16X0.14 [PVC]
More info
▲| Product type | System cable |
| Data management status | |
| Article revision | 03 |
| Ambient conditions | |
| Degree of protection | IP00 |
| Degree of protection (Installation location) | ≥ IP54 (Installation location) |
| Ambient temperature (operation) | -40 °C ... 70 °C (fixed installation) |
| -10 °C ... 70 °C (flexible installation) | |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Operating voltage (AC) | ≤ 30 V AC |
| Operating voltage (DC) | ≤ 60 V DC |
| Nominal operating mode | 100% operating factor |
| Current (Per path, 50°C) | ≤ 1 A (Uncoiled, see derating) |
| Current (Per path, 70°C) | ≤ 0.6 A (Uncoiled, see derating) |
| Cable length | 10 m |
| 16X0.14 [PVC] | |
| Number of positions | 16 |
| Shielded | yes |
| Cable type | 16X0.14 [PVC] |
| Conductor type | Assembled shielded round cable |
| Conductor structure signal line | 7x 0.16 mm |
| AWG signal line | 26 |
| Conductor cross section | 16x 0.14 mm² |
| Wire diameter incl. insulation | 1 mm ±0.03 mm |
| External cable diameter | 7.00 mm ±0.4 mm |
| Outer sheath, material | Semi-rigid PVC |
| External sheath, color | gray |
| Conductor material | Tin-plated Cu litz wires |
| Cable resistance | ≤ 145 Ω/km (20 °C) |
| Insulation resistance | ≥ 20 MΩ*km (20 °C) |
| Smallest bending radius, fixed installation | 74 mm |
| Smallest bending radius, movable installation | 133 mm |
| Dynamic load capacity (bending) | Max. bending cycles: 5000 (at a radius of ≥ 15x outside diameter) |
| Halogen-free | no |
| Flame resistance | IEC 60332-1-2 (raw cable) |
| VDE 0842, Part 332-1-2 (raw cable) | |
| IEC 60332-3-22 (raw cable) | |
| UL VW-1 | |
| CSA FT-1 | |
| Resistance to oil | can withstand occasional splashes (raw cable) |
| Connection 1 | |
| Connection in acc. with standard | IEC 60807-2 |
| DIN 41652 | |
| Connection method | D-SUB socket strip |
| Screw thread | UNC 4-40 |
| M2,5 | |
| Number of connections | 1 |
| Number of positions | 25 |
| Tightening torque | 0.2 Nm |
| Insertion/withdrawal cycles | > 200 |
| Pitch | 2.77 mm |
| Connection 2 | |
| Connection in acc. with standard | based on IEC 60603-13 |
| Connection method | IDC/FLK socket strip |
| Number of connections | 1 |
| Number of positions | 16 |
| Insertion/withdrawal cycles | > 50 |
| Pitch | 2.54 mm |
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |