View larger
IL PN BK DI8 DO4 2TX-PAC 2703994 PHOENIX CONTACT Bus coupler
IL PN BK DI8 DO4 2TX-PAC
2703994
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Bus coupler designed by Phoenix Contact and marked with part number IL PN BK DI8 DO4 2TX-PAC integrates digital inputs and outputs directly into PROFINET network environments. Network couplers of this style coordinate local I/O expansion modules with industrial controllers to manage discrete automation tasks efficiently. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- IO link master (EF007298): No
- System accessory (EF004118): Yes
- Degree of protection (IP) (EF005474): IP20
- With potential separation (EF003272): No
- Suitable for rail mounting (EF003972): Yes
- Wall mounting/direct mounting (EF007020): No
- Front built-in possible (EF007016): No
- Rack-assembly possible (EF007018): No
- Suitable for safety functions (EF001597): No
- Appendant operation agent (Ex ia) (EF004141): No
- Appendant operation agent (Ex ib) (EF004142): No
More info
▲Key Commercial Data
| Orderkey | 2703994 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 128 (C-6-2017) |
| GTIN | 4046356041164 |
| Weight per Piece (excluding packing) | 335.700 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 80 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Specfications with connectors |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail mounting |
|---|---|
| Net weight | 335.7 g |
| Note on weight specifications | with connectors |
| Diagnostics messages | Short-circuit / overload of the digital outputs Yes |
| Sensor supply failure Yes | |
| Failure of the actuator supply Yes | |
| Mounting type | DIN rail mounting |
Interfaces
| Designation | PROFINET |
|---|---|
| No. of channels | 2 |
| Connection method | RJ45 socket, auto negotiation |
| Transmission speed | 100 Mbps (acc. to PROFINET standard) |
| Transmission physics | Ethernet in RJ45 twisted pair |
| Designation | Inline local bus |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps / 2 Mbps (automatic detection, no combined system) |
System limits of the bus coupler
| Amount of process data | max. 488 Byte (max. 244 bytes IN - max. 244 bytes OUT) |
|---|---|
| max. 244 Byte (Input) | |
| max. 244 Byte (Output) | |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 61 (on board I/Os are two devices) |
| Number of devices with parameter channel | max. 16 |
| Number of supported branch terminals with remote bus branch | 0 |
Power supply for module electronics
| Connection method | Spring-cage connection |
|---|---|
| Designation | Bus coupler supply UBC; Communications power UL(7.5 V) and the analog supply UANA(24 V) are generated from the bus coupler supply. |
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Supply current | 138 mA |
| Current consumption | typ. 138 mA (from UBK) |
| max. 0.91 A DC (from UBK) | |
| Power dissipation | typ. 3 W (entire device) |
Inline potentials
| Designation | Bus coupler supply UBC; Communications power UL(7.5 V) and the analog supply UANA(24 V) are generated from the bus coupler supply. |
|---|---|
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (via Inline connector) |
| Current consumption | 138 mA (without connected I/O terminal blocks) |
| typ. 138 mA | |
| max. 0.91 A DC | |
| Designation | Communications power (UL) |
| Supply voltage | 7.5 V DC ±5 % |
| Power supply unit | max. 0.8 A DC (observe derating) |
| Power consumption | typ. 3 W (entire device) |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 0.5 A DC (observe derating) |
| Designation | Main circuit supply (UM) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 8 A DC (Sum of UM+ US; 4 A, maximum, when used in potentially explosive areas.) |
| Current consumption | 3 mA (without sensors) |
| max. 8 A DC | |
| Designation | Segment circuit supply (US) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 8 A DC (Sum of UM+ US; 4 A, maximum, when used in potentially explosive areas.) |
| Current consumption | max. 8 A DC |
| Power consumption | typ. 3 W (entire device) |
| Current consumption | 3 mA (without actuators) |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | EN 61131-2 type 1 |
| Connection method | Inline connector |
| Connection technology | 2, 3-wire |
| Number of inputs | 8 |
| Typical response time | approx. 500 µs |
| Type of protection | Reverse polarity protection |
| Filter time | 3 ms |
| Input voltage | 24 V DC |
| Input voltage range "0" signal | -30 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Nominal input current at UIN | typ. 3 mA |
| Typical input current per channel | typ. 3 mA |
| Delay at signal change from 0 to 1 | 5 ms |
| Delay at signal change from 1 to 0 | 5 ms |
Digital outputs
| Output name | Digital outputs |
|---|---|
| Connection method | Inline connector |
| Connection technology | 2, 3-wire |
| Number of outputs | 4 |
| Type of protection | Short-circuit and overload protection |
| Output voltage | 24 V DC -1 V (At nominal current) |
| Nominal output voltage | 24 V DC |
| Maximum output current per channel | 500 mA |
| Maximum output current per module / terminal block | 2 A |
| Maximum output current per module | 2 A |
| Nominal load, inductive | 12 VA (1.2 H, 48 Ω) |
| Nominal load, lamp | 12 W |
| Nominal load, ohmic | 12 W |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |