BTP 3,5 3281116 PHOENIX CONTACT Feed-through terminal block
BTP 3,5
3281116
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact BTP 3,5 feed-through terminal block provides reliable conductor termination for industrial automation and machinery control panels. Terminal blocks ensure safe, organized electrical connectivity inside complex enclosures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 3281116
- Packing unit: 50 pc
- Minimum order quantity: 50 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 391 (C-1-2017)
- GTIN: 4055626119175
- Weight per Piece (excluding packing): 11.320 g
- Custom tariff number: 85369010
- Country of origin: PL (Poland)
- Number of levels: 1
- Number of connections: 4
- Potentials: 1
- Nominal cross section: 4 mm²
- Color: black
- Insulating material: PC
- Flammability rating according to UL 94: V0
More info
▲Key Commercial Data
| Orderkey | 3281116 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 391 (C-1-2017) |
| GTIN | 4055626119175 |
| Weight per Piece (excluding packing) | 11.320 g |
| Custom tariff number | 85369010 |
| Country of origin | PL (Poland) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 4 |
| Potentials | 1 |
| Nominal cross section | 4 mm² |
| Color | black |
| Insulating material | PC |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | IIIa |
| Maximum power dissipation for nominal condition | 1.02 W |
| Ambient temperature (operation) | -40 °C ... 110 °C |
| Maximum load current | 32 A (The maximum load current must not be exceeded by the total current of all connected conductors.) |
| Nominal current IN | 32 A |
| Nominal voltage UN | 690 V |
| Open side panel | Yes |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.2 mm² / 0.2 kg |
| 4 mm² / 0.9 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.2 mm² |
| Tractive force setpoint | 10 N |
| Conductor cross section tensile test | 4 mm² |
| Tractive force setpoint | 60 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 35 |
| Setpoint | 1 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 0.48 kA |
| Result of thermal test | Test passed |
| Ageing test for screwless modular terminal block temperature cycles | 192 |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Result of aging test | Test passed |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 2, bogie-mounted |
| Test frequency | f1= 5 Hz to f2= 250 Hz |
| ASD level | 6.12 (m/s2)2/Hz |
| Acceleration | 3.12 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 30g |
| Shock duration | 18 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
Connection data
| Connection method | Push-in connection |
|---|---|
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Min. AWG conductor cross section, flexible | 24 |
| Max. AWG conductor cross section, flexible | 12 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 2.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
| Stripping length | 10 mm ... 12 mm |
Connection data (JIS standard)
| Connection method | Push-in connection |
|---|---|
| Connection in acc. with standard | JIS 8207-7-1 |
| Single-wire/terminal point, solid diameter min. | 0.5 mm |
| Single-wire/terminal point, solid diameter max. | 2 mm |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 3.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 2 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2 mm² |
| Connection cross sections directly pluggable | 0.8 mm 2 mm |
| Single-wire/terminal point, solid diameter min. | 0.8 mm |
| Single-wire/terminal point, solid diameter max. | 2 mm |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 2 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2 mm² |
| Nominal current IN | 30 A |
| Maximum load current | 30 A |
| Nominal voltage UN | 600 V |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-1 |
|---|---|
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |