View larger
BASE-MSTB/D37M/16CH/EX 1065476 PHOENIX CONTACT 16-channel Marshalling VIP I/O base element with 37-pin D-SUB..
BASE-MSTB/D37M/16CH/EX
1065476
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The BASE-MSTB/D37M/16CH/EX 16-channel Marshalling VIP I/O base element with 37-pin D-SUB from Phoenix Contact streamlines signal distribution between field instrumentation and control systems. Marshalling bases are standard in process automation for cross-wiring signals efficiently while maintaining hazardous area compliance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Type: Modular Brackets
- Product Family: VIP I/O-Marshalling
- Number of channels: 16
- Insulation Properties Surge Category: II, III
- Degree of pollution: 2
- Number of channels: 16
- Maximum operating voltage U Max.: 30 V DC (P2 and Field Terminals)
- Max. permissible current: 15 A (P1- or P2- terminals)
- Maximum permissible sum current: 15 A (per module)
- Max. current capacity per shunt: 3 A (Field Signal)
- AWG Conductor Section: (Converted according to IEC)
- Field Level Standard-compliant connection: IEC/EN
- Connection type: Plug
- Number of connections: 4
- Number of poles: 16
- Level of control Connection type: D-SUB Male Connector
More info
▲| Product Type | Modular Brackets |
| Product Family | VIP I/O-Marshalling |
| Number of channels | 16 |
| Insulation Properties | |
| Surge Category | II, III |
| Degree of pollution | 2 |
| Number of channels | 16 |
| Maximum operating voltage UMax. | 30 V DC (P2 and Field Terminals) |
| 230 V AC (P2 and field terminals) | |
| 30 V DC (P1 terminals) | |
| 30 V DC (D-SUB) | |
| Max. permissible current | 15 A (P1- or P2- terminals) |
| Maximum permissible sum current | 15 A (per module) |
| Max. current capacity per shunt | 3 A (Field Signal) |
| 1 A (Control Contacts) |
| AWG Conductor Section | (Converted according to IEC) |
| Field Level | |
| Standard-compliant connection | IEC/EN |
| Connection type | Plug |
| Number of connections | 4 |
| Number of poles | 16 |
| Level of control | |
| Connection type | D-SUB Male Connector |
| Number of connections | 1 |
| Number of poles | 50 |
| Technical Safety Data | |
| Input voltage Ui | 30 V (per channel) |
| Input Current Ii | 1 A (per channel) |
| Li Inductance | 0 mH |
| Ci Capacity | 0 μF |
| Maximum safety voltage Um | 253 V AC |
| Status Indication | No |
| Available Status Indication | No |
| Item Dimensions | |
| Width | 250 mm |
| Height | 142.3 mm |
| Depth | 78 mm |
| Environmental conditions | |
| Protection Index | IP20 |
| Ambient Temperature (Service) | -40 °C ... 70 °C |
| Ambient Temperature (Storage/Transport) | -40 °C ... 70 °C |
| Altitude | < 2000 m |
| Permissible air humidity (service) | 0 % ... 95% (non-condensing) |
| ATEX | |
| Marked | II 3G Ex ec IIC T4 Gc |
| Certificate | CSANe 22ATEX1005X |
| IECEx | |
| Marked | Ex ec IIC T4 Gc |
| Certificate | IECEx CSA 22.0004X |
| UKEX | |
| Marked | II 3G Ex ec IIC T4 Gc |
| Certificate | CSAE 22UKEX1040X |
| CSA, USA/Canada | |
| Marked | Class I, Div. 2 Groups A, B, C, D T4 Class I, Zone 2, AEx ec IIC T4 Gc Ex ec IIC T4 Gc |
| Certificate | CSA 22CA80084549X |
| Type of mounting | Rail mounting |
| Position for mounting | Optionally on 35 mm rail according to EN 60715 |