View larger
PT 2X2-BE 2839208 PHOENIX CONTACT Surge protection base element
PT 2X2-BE
2839208
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed as a robust mounting receptacle, the Phoenix Contact PT 2X2-BE surge protection base element accommodates multi-line plug-in surge protection blocks within industrial control layouts. This category of component ensures stable mechanical seating and secure screw or spring-cage connections for ongoing operational safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2839208
- Packing unit: 10 pc
- Catalog page: Page 99 (C-4-2017)
- GTIN: 4017918182748
- Weight per Piece (excluding packing): 50.230 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 90 mm
- Width: 17.7 mm
- Depth: 51.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 1 Div.
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PA 6.6
More info
▲Key Commercial Data
| Orderkey | 2839208 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 99 (C-4-2017) |
| GTIN | 4017918182748 |
| Weight per Piece (excluding packing) | 50.230 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Standards for cearances and creepage distances | VDE 0110-1 |
| Mounting type | DIN rail: 35 mm |
| Type | Base element, DIN rail mounting |
| Number of positions | 4 |
Protective circuit
| Nominal voltage UN | 24 V AC |
|---|---|
| 24 V DC | |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 450 mA (45°C) |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |