View larger
PT 4-EX(I)-BE 2839486 PHOENIX CONTACT Surge protection base element
PT 4-EX(I)-BE
2839486
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Supplied by Phoenix Contact, the PT 4-EX(I)-BE 2839486 PHOENIX CONTACT Surge protection base element is a DIN rail mountable base element for modular plug-in surge arresters. These mounting bases retain field wiring and allow quick replacement of protective plug modules without interrupting signal loops. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Base element
- Product family: PLUGTRAB PT
- Type: Base element, DIN rail mounting
- Number of positions: 4
- Wire pairs per module: 2
- Data management status Article revision: 23
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 24 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Maximum inner capacitance C i: 1.1 nF
More info
▲| Product type | Base element |
| Product family | PLUGTRAB PT |
| Type | Base element, DIN rail mounting |
| Number of positions | 4 |
| Wire pairs per module | 2 |
| Data management status | |
| Article revision | 23 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Maximum inner capacitance Ci | 1.1 nF |
| Max. internal inductance Li | 1 µH |
| Max. input current Ii | 500 mA (T4 / ≤ 80°C) |
| 500 mA (T5 / ≤ 55 °C) | |
| 500 mA (T6 / ≤ 40 °C) | |
| Max. input voltage Ui | 30 V DC |
| max. input power Pi | 850.00 mW (T4 / ≤ 80°C) |
| 700.00 mW (T5 / ≤ 55 °C) | |
| 700.00 mW (T6 / ≤ 40 °C) | |
| Maximum inner time factor (Ri/Li) | ≤ 10 µs |
| Ambient temperature (operation) | -40 °C ... 80 °C (T4) |
| -40 °C ... 55 °C (T5) | |
| -40 °C ... 40 °C (T6) |
| Dimensional drawing | |
| Width | 17.7 mm |
| Height | 90 mm |
| Depth | 51.5 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 1 Div. |
| Color | blue (RAL 5015) |
| Copper color | |
| Flammability rating according to UL 94 | V-0 |
| Housing material | PA 6.6 |
| Mechanical data | |
| Open side panel | No |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 500 mA (40 °C) |
| Resistance per path | 0 Ω |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl) |
| Conformity/Approvals | |
| ATEX | II 1 G Ex ia IIC T4...T6 |
| II 1 D Ex iaD 20 IP6x T85 °C...135 °C | |
| Standards/specifications | EN 61643-21 |
| Note | A2:2013 |
| Standards/specifications | EN 60079-0 |
| Note | 2018 |
| Standards/specifications | EN 60079-11 |
| Note | 2012 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-11 |
| Note | 2011 |
| Mounting type | DIN rail: 35 mm |