View larger
PT 2XEX(I)-BE 2839279 PHOENIX CONTACT Surge protection base element
PT 2XEX(I)-BE
2839279
PHOENIX CONTACT
10 Pcs.
Automation > Accessories/spare parts for surge protection data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for hazardous environments, the Phoenix Contact PT 2XEX(I)-BE surge protection base element supports intrinsic safety applications by holding specialized protective plugs in process automation networks. These specialized bases maintain strict separation requirements for circuits operating in potentially explosive atmospheres. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2839279
- Packing unit: 10 pc
- Catalog page: Page 132 (C-4-2017)
- GTIN: 4017918182885
- Weight per Piece (excluding packing): 62.430 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 90 mm
- Width: 17.7 mm
- Depth: 51.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 1 Div.
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PA 6.6
More info
▲Key Commercial Data
| Orderkey | 2839279 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 132 (C-4-2017) |
| GTIN | 4017918182885 |
| Weight per Piece (excluding packing) | 62.430 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | sky blue RAL 5015 |
| Mounting type | DIN rail: 35 mm |
| Type | Base element, DIN rail mounting |
| Number of positions | 4 |
Protective circuit
| Nominal voltage UN | 24 V DC |
|---|---|
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 325 mA (≤40 °C) |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | EN 61643-21 A2:2013 |
|---|---|
| EN 60079-0 2012 | |
| EN 60079-11 2012 | |
| EN 60079-26 2007 | |
| IEC 60079-0 2011 | |
| IEC 60079-11 2011 | |
| IEC 60079-26 2006 |
General
| Maximum inner capacitance Ci | 1.3 nF |
|---|---|
| Max. internal inductance Li | 1 µH |
| Maximum inner time factor (Ri/Li) | ≤ 0.2 µs |
| Max. input current Ii | 325 mA (T4 / ≤ 80°C) |
| 325 mA (T5 / ≤ 55 °C) | |
| 325 mA (T6 / ≤ 40 °C) | |
| Max. input voltage Ui | 30 V DC |
| max. input power Pi | 3 W |
| Ambient temperature (operation) | -40 °C ... 80 °C (T4) |
| -40 °C ... 55 °C (T5) | |
| -40 °C ... 40 °C (T6) |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |