Safety module Axioline F, Digital input module, Functional safety, SafetyBridge technology, Digital inputs: 4 (With 2-channel assignment), 8 (With 1-channel assignment), 24 V DC, connection technology: 2, 3, 4 drivers, protection index: IP20

Automation > Fieldbus, decentr. periphery - digital I/O module
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Designed for safety-critical machine installations, the Phoenix Contact AXL F SSDI8/4 1F Safety module monitors critical binary signals to help prevent hazardous conditions in automated environments. Safety modules of this type process sensor inputs to ensure reliable emergency stops and protective interlocks.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage DC (EF007534): 19.2 V
  • Voltage type (supply voltage) (EF002991): DC
  • Number of digital inputs (EF001992): 4
  • Number of digital outputs (EF001993): 0
  • Digital inputs configurable (EF008516): No
  • Digital outputs configurable (EF008520): No
  • Input current at signal 1 (EF001428): 0.0042 mA
  • Permitted voltage at input (EF007554): 24 V
  • Type of voltage (input voltage) (EF003033): DC
  • Short-circuit protection, outputs available (EF003203): No
  • Number of HW-interfaces industrial Ethernet (EF003020): 0
  • Number of interfaces PROFINET (EF006932): 0
  • Number of HW-interfaces RS-232 (EF003021): 0
  • Number of HW-interfaces RS-422 (EF003022): 0
  • Number of HW-interfaces RS-485 (EF003023): 0
  • Number of HW-interfaces serial TTY (EF003024): 0

More info

▲

Key Commercial Data

Orderkey2702263
Packing unit1 pc
Catalog pagePage 301 (C-6-2017)
GTIN4055626066813
Weight per Piece (excluding packing)347.600 g
Custom tariff number85389091
Country of originDE (Germany)

Dimensions

Dimensional drawing
Width53.6 mm
Height126.1 mm
Depth54 mm
Note on dimensionsHousing dimensions

Ambient conditions

Ambient temperature (operation)-35 °C ... 60 °C (Mounting position: any)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 75 % (on average, 85% infrequently, non-condensing)
Permissible humidity (storage/transport)10 % ... 75 % (non-condensing)
Air pressure (operation)70 kPa ... 108 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)66 kPa ... 108 kPa (up to 3500 m above sea level)
Degree of protectionIP20

Interfaces

DesignationAxioline F local bus
No. of channels1
Connection methodBus base module

Digital inputs

Input nameDigital inputs
Description of the inputIEC 61131-2 type 3
Connection methodPush-in connection
Connection technology2, 3, 4-wire
Number of inputs4 (with two-channel assignment)
8 (for single-channel assignment)
Input filter time1.5 ms
Input voltage24 V DC (via clock outputs T1 and T2 or external supply)
Input voltage range-3 V DC ... 30.2 V DC
Nominal input current at UINtyp. 4.2 mA
Typical input current per channel4.2 mA

General

Mounting typeDIN rail
Net weight347.6 g
Note on weight specificationswith connectors and bus base module

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptiontyp. 280 mA (all inputs set; power supply by UIof 19.2 V DC to 30.2 V DC)
max. 310 mA
DesignationSupply for digital input modules (UI)
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 9 mA (all inputs set; power supply by UIwith 30.2 V DC; without power supply to the sensors via clock supplies T1 and T2)
Type of protectionProtection against polarity reversal, EMC protective circuit, undervoltage detection

Safety-related characteristic data

DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)max. 3 (two channel; dependent in parameterization and wiring)
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)max. 3 (two channel; dependent in parameterization and wiring)
DesignationEN ISO 13849
Performance level (PL)max. e (two channel; dependent in parameterization and wiring)
Categorymax. 4 (two channel; dependent in parameterization and wiring)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)max. 3 (two channel; dependent in parameterization and wiring)

Standards and Regulations

Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e