Deploying the Phoenix Contact AXL F SGI2 1H I/O module allows industrial engineers to expand control architectures for signal acquisition and processing. Such modules bridge field devices with central controllers to maintain stable communication in automated industrial environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2702911
- Packing unit: 1 pc
- GTIN: 4055626459288
- Weight per Piece (excluding packing): 187.700 g
- Custom tariff number: 85389091
- Country of origin: DE (Germany)
- Width: 35 mm
- Height: 126.1 mm
- Depth: 54 mm
- Note on dimensions: The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
- Ambient temperature (operation): -25 °C ... 60 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Permissible humidity (operation): 5 % ... 95 % (non-condensing)
- Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
- Air pressure (operation): 70 kPa ... 106 kPa (up to 3000 m above sea level)
- Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000 m above sea level)
More info
▲Key Commercial Data
| Orderkey | 2702911 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626459288 |
| Weight per Piece (excluding packing) | 187.700 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 35 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 187.7 g |
| Note on weight specifications | with connectors and bus base module |
| Operating mode | Process data mode with 6 words |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | typ. 65 mA |
| max. 75 mA | |
| Power consumption | typ. 325 mW |
| max. 375 mW | |
| Designation | Supply for analog modules (UA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 25 mA (with typical load: 1 weighing cell with 350 Ω, only one channel loaded) |
| typ. 55 mA (with maximum load: 8 weighing cells with 350 Ω, only one channel loaded) | |
| typ. 110 mA (with maximum load: 8 weighing cells with 350 Ω per channel) | |
| Power consumption | typ. 2.6 W (with maximum load: 8 weighing cells with 350 Ω per channel) |
| typ. 1.5 W (entire device) | |
| max. 3 W (entire device) | |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage |
Contacts
| Description | Floating N/O contact |
|---|---|
| Quantity | 2 (Ka1-Kb1, Ka2-Kb2) |
| Contact resistance | < 1 Ω (typical) |
| Typical response time | typ. 0.2 ms (opening) |
Analog inputs
| Description of the input | Input channels for strain gauge |
|---|---|
| Number of inputs | 2 |
| Connection technology | 6 or 4-wire, twisted pair shielded cable |
| Bridge difference Ud | Measuring range specified by selecting the characteristic |
| Bridge voltage U0 | 5 V |
| Characteristics | can be parameterized: 350 μV/V ... 6500 μV/V |
| Measured value representation | 32 bits |
Analog outputs
| Output description | Jumper supply |
|---|---|
| Number of outputs | 2 |
| Impedance | > 43 Ω (per channel) |
| Output voltage | typ. 5 V |
| Output current | max. 115 mA (per channel) |
Electrical isolation
| Test section | Logic 500 V AC 50 Hz 1 min. |
|---|---|
| 24 V supply (I/O) 500 V AC 50 Hz 1 min. | |
| Analog inputs 500 V AC 50 Hz 1 min. | |
| N/O contact Ka1- Kb1500 V AC 50 Hz 1 min. | |
| N/O contact Ka2- Kb2500 V AC 50 Hz 1 min. | |
| Functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |