View larger
AXL F RTD4 XC 1H 1035430 PHOENIX CONTACT I/O module
AXL F RTD4 XC 1H
1035430
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed by Phoenix Contact, the AXL F RTD4 XC 1H is an advanced I/O module engineered to interface temperature sensors with industrial control backplanes. Such input modules are widely deployed in process monitoring, environmental chambers, and thermal management loops where precise resistance temperature detector measurements are critical. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): Yes
- Input, resistance thermometer (EF003207): Yes
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Resolution of the analogue inputs (EF003575): 24 Bit
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): No
More info
▲Key Commercial Data
| Orderkey | 1035430 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626541839 |
| Weight per Piece (excluding packing) | 144.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Caption | Dimensional drawing |
| Width | 35 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C (Standard) |
|---|---|
| -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Connection data
| Designation | Axioline F connector |
|---|---|
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 144 g |
| Note on weight specifications | with connectors and bus base module |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | max. 140 mA |
| Power consumption | max. 700 mW |
| Designation | Supply for analog modules (UA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | max. 17 mA |
| Power consumption | max. 400 mW |
| max. 1.1 W (at UBusand UA) | |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage | |
| Transient protection supply voltage |
Analog inputs
| Number of inputs | 4 (for resistance temperature detectors) |
|---|---|
| Input name | Analog inputs |
| Description of the input | Inputs for resistive temperature sensors |
| Connection method | Spring-cage connection with direct connector-in method |
| Connection technology | 2, 3, 4-wire (shielded) |
| Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors |
| Linear resistance measuring range | 0 Ω ... 500 Ω |
| 0 kΩ ... 5 kΩ | |
| Nominal value of the current sources | 1 mA (Pt 100, Ni 100, RLin500 Ω; pulse current, the specification is valid during the sampling phase) |
| Measured value representation | 16 bits (15 bits + sign bit) |
| Resolution A/D | 24 bit |
| Type of protection | Short-circuit protection, overload protection of the inputs |
| Transient protection of inputs | |
| Transient protection of sensor supplies | |
| Data formats | IB IL, S7-compatible |
| Input filter time | 40 ms |
Electrical isolation
| Test section | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |