PHOENIX CONTACT AXL F LPSDO8/3 1F AXL F LPSDO8/3 1F 2702171 PHOENIX CONTACT Safety module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL F LPSDO8/3 1F 2702171 PHOENIX CONTACT Safety module

AXL F LPSDO8/3 1F

2702171

PHOENIX CONTACT

1 Pcs.

Safety module Safety-oriented digital output module, IP20 degree of protection, for the SafetyBridge system. The module has 4 secure digital outputs with two-channel occupancy or 8 secure digital outputs with single-channel occupancy Axioline F, Digital Output Module, Functional Safety, SafetyBridge Solution, Digital Outputs: 4 (With 2-channel assignment), 8 (With 1-channel assignment), 2 A, protection rating: IP20

Automation > Fieldbus, decentr. periphery - digital I/O module
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact AXL F LPSDO8/3 1F safety module monitors and executes safety-related switching functions within modular automation stations, protecting personnel and machinery in hazardous states. Safety output modules ensure reliable de-energization of connected loads when emergency stop or safety interlock conditions are triggered.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage DC (EF007534): 19.2 V
  • Voltage type (supply voltage) (EF002991): DC
  • Number of digital inputs (EF001992): 0
  • Number of digital outputs (EF001993): 4
  • Digital inputs configurable (EF008516): No
  • Digital outputs configurable (EF008520): No
  • Type of voltage (input voltage) (EF003033): DC
  • Output current (EF003202): 2 A
  • Permitted voltage at output (EF007553): 24 V
  • Short-circuit protection, outputs available (EF003203): No
  • Number of HW-interfaces industrial Ethernet (EF003020): 0
  • Number of interfaces PROFINET (EF006932): 0
  • Number of HW-interfaces RS-232 (EF003021): 0
  • Number of HW-interfaces RS-422 (EF003022): 0
  • Number of HW-interfaces RS-485 (EF003023): 0
  • Number of HW-interfaces serial TTY (EF003024): 0

More info

▲

Key Commercial Data

Orderkey2702171
Packing unit1 pc
Catalog pagePage 300 (C-6-2017)
GTIN4055626004983
Weight per Piece (excluding packing)222.000 g
Custom tariff number85389091
Country of originDE (Germany)

Dimensions

Dimensional drawing
Width53.6 mm
Height126.1 mm
Depth54 mm
Note on dimensionsHousing dimensions

Ambient conditions

Ambient temperature (operation)-35 °C ... 60 °C (Mounting position: any)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 75 % (on average, 85% infrequently, non-condensing)
Permissible humidity (storage/transport)10 % ... 75 % (non-condensing)
Air pressure (operation)70 kPa ... 108 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)66 kPa ... 108 kPa (up to 3500 m above sea level)
Degree of protectionIP20

Interfaces

DesignationAxioline F local bus
No. of channels1
Connection methodBus base module

Digital outputs

Output nameDigital outputs
Connection methodDirect plug-in technology
Connection technology2, 3-wire
Number of outputs4 (with two-channel assignment)
8
Type of protectionOverload protection, freewheeling circuit for inductive loads,
Discharge circuit for accelerated discharge of capacitive loads
Output voltage24 V DC
Output currentmax. 2 A (per channel)
max. 1.5 A (per channel according to CULUS)
max. 4 A (per group)
max. 3 A (per group according to CULUS)
max. 8 A (Total current of all outputs; Please observe the notes in the user manual.)
max. 6 A (Total current of all outputs according to CULUS)
Maximum output current per channel2 A
Maximum output current per module / terminal block8 A

General

Mounting typeDIN rail
Net weight222 g
Note on weight specificationswith connectors and bus base module

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptiontyp. 260 mA (all outputs set; power supply by UOof 19.2 V DC to 30.2 V DC)
max. 280 mA
DesignationSupply for digital output modules (UO)
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 25 mA (all outputs set; power supply by UOwith 30.2 V DC; without power supply to the actuator)
Type of protectionProtection against polarity reversal, EMC protective circuit, undervoltage detection

SafetyBridge properties

Connection to I/O modulesmax. 16 (safe digital I/O modules)
Logic memory30 kByte

Safety-related characteristic data

DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)max. 3 (two channel; dependent in parameterization and wiring)
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)max. 3 (two channel; dependent in parameterization and wiring)
DesignationEN ISO 13849
Performance level (PL)max. e (two channel; dependent in parameterization and wiring)
Categorymax. 4 (two channel; dependent in parameterization and wiring)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)max. 3 (two channel; dependent in parameterization and wiring)

Standards and Regulations

Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.