View larger
AXL F AI2 AO2 XC 1H 1035429 PHOENIX CONTACT I/O module
AXL F AI2 AO2 XC 1H
1035429
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for robust environments, the Phoenix Contact AXL F AI2 AO2 XC 1H I/O module handles mixed analog inputs and outputs with extended environmental resilience. Such ruggedized modules ensure reliable signal processing in harsh industrial conditions subject to extreme temperatures or vibration.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): Yes
- Input, voltage (EF003205): Yes
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): Yes
- Resolution of the analogue inputs (EF003575): 16 Bit
- Output, current (EF003212): Yes
- Output, voltage (EF003213): Yes
- Output signal configurable (EF003214): Yes
- Resolution of the analogue outputs (EF003577): 16 Bit
- Number of analogue inputs (EF001994): 2
- Number of analogue outputs (EF001995): 2
- Analogue inputs configurable (EF008518): Yes
More info
▲Key Commercial Data
| Orderkey | 1035429 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4055626541792 |
| Weight per Piece (excluding packing) | 197.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Caption | Dimensional drawing |
| Width | 35 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C (Standard) |
|---|---|
| -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Connection data
| Designation | Axioline F connector |
|---|---|
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 197 g |
| Note on weight specifications | with connectors and bus base module |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | typ. 120 mA |
| max. 150 mA | |
| Power consumption | typ. 0.6 W |
| max. 0.75 W | |
| Designation | Supply for analog modules (UA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 40 mA |
| max. 80 mA | |
| Power consumption | max. 1.92 W |
| typ. 1.56 W (at UBusand UA) | |
| max. 2.67 W (at UBusand UA) | |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage | |
| Transient protection supply voltage |
Analog inputs
| Description of the input | Differential inputs, voltage or current can be chosen separately |
|---|---|
| Input name | Analog inputs |
| Number of inputs | 2 |
| Connection method | Push-in connection |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded, twisted pair |
| A/D conversion time | 2 µs |
| Resolution A/D | 16 bit |
| Limit frequency (3 dB) | 30 Hz |
| 12 kHz | |
| Type of protection | Transient protection of inputs |
| Overload protection of the current inputs | |
| Overload protection of the voltage inputs | |
| Data formats | IB IL, S7-compatible, standardized representation |
| Measured value representation | 16 bits (15 bits + sign bit) |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| -20 mA ... 20 mA | |
| Input resistance current input | 104 Ω (typical) |
| Voltage input signal | 0 V ... 5 V |
| -5 V ... 5 V | |
| 0 V ... 10 V | |
| -10 V ... 10 V | |
| Input resistance of voltage input | 268 kΩ (typical) |
| Common mode voltage range signal - ground | -50 V DC ... 50 V DC |
| Input filter | 30 Hz, 12 kHz and mean-value generation (can be parameterized) |
Analog outputs
| Number of outputs | 2 |
|---|---|
| Connection method | Push-in connection |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded, twisted pair |
| Output name | Analog outputs |
| D/A resolution | 16 bit |
| Type of protection | Short-circuit and overload protection |
| Transient protection | |
| Protective circuit/component | electronic |
| Suppressor diode | |
| Data formats | IB IL, S7-compatible, standardized representation |
| Representation of output values | 16 bits (15 bits + sign) |
| Process data update | 150 µs |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| -20 mA ... 20 mA | |
| Load/output load current output | ≤ 500 Ω |
| Voltage output signal | 0 V ... 5 V |
| -5 V ... 5 V | |
| 0 V ... 10 V | |
| -10 V ... 10 V | |
| Load/output load voltage output | > 2 kΩ |
| Precision | typ. 0.1 % (of output range final value) |
Electrical isolation
| Test section | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply (logic)/analog inputs and outputs 500 V AC 50 Hz 1 min. | |
| 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O)/analog inputs and outputs 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. | |
| Analog inputs and outputs/functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |