PHOENIX CONTACT AXL E IOL SDI8 SDO4 2A M12 L AXL E IOL SDI8 SDO4 2A M12 L 1185380 PHOENIX CONTACT Axioline E safety module, 4 secure digital inputs with .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL E IOL SDI8 SDO4 2A M12 L 1185380 PHOENIX CONTACT Axioline E safety module, 4 secure digital inputs with ..

AXL E IOL SDI8 SDO4 2A M12 L

1185380

PHOENIX CONTACT

1 Pcs.

Axioline E safety module, 4 secure digital inputs with 2-channel occupancy, 8 safe digital inputs with single-channel occupancy, 4 safe digital outputs with +/- switching, IO-Link interface, IP65/IP67 rating, for PROFIsafe systems Axioline E Safety Module, 4 Secure Digital Inputs with 2 Channel Occupancy, 8 Secure Digital Inputs with One Channel Occupancy, 4 Safe Digital Outputs with +/- Switching, IO-Link Interface, IP65/IP67 Degree of Protection, for PROFIsafe Systems

Automation > Fieldbus, decentr. periphery - digital I/O module
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Designed for decentralized automation architectures, the Phoenix Contact AXL E IOL SDI8 SDO4 2A M12 L Axioline E safety module provides secure signal processing directly in the field. Fieldbus safety modules offer robust environmental resistance while maintaining reliable communication of safety-related digital inputs and outputs.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Width: 59.8 mm
  • Height: 214 mm
  • Depth: 30 mm
  • Note on Measurement Indications: Data incl. fixing tabs and plugs
  • Shell material: Plastic POCAN B4239 GF30 YE 1018
  • Digital Denomination Entry: Secure Digital Inputs
  • Ticket Description: IEC 61131-2 Type 3
  • Number of Entries: 4 (With 2 channel assignment)
  • Cable length: max. 200 m
  • Connection type: M12 plug-in connector (A-coded)
  • Connection technology: 3 conductors
  • Input Voltage Range Signal "0": -30 V DC ... 5 V DC
  • Input Voltage Range Signal "1": 11 V DC ... 30.2 V DC
  • Nominal Input Voltage U IN: 24 V DC
  • Nominal input current to U IN: Typ. 3.7 mA (with 24 V DC)
  • Inlet Filter Time: 1.5 ms

More info

▲
Technical data

Dimensions
Dimension Scheme
Width59.8 mm
Height214 mm
Depth30 mm
Note on Measurement IndicationsData incl. fixing tabs and plugs

Material Data
Shell materialPlastic POCAN B4239 GF30 YE 1018

Input data
Digital
Denomination EntrySecure Digital Inputs
Ticket DescriptionIEC 61131-2 Type 3
Number of Entries4 (With 2 channel assignment)
8 (With 1 channel assignment)
Cable lengthmax. 200 m
Connection typeM12 plug-in connector (A-coded)
Connection technology3 conductors
Input Voltage Range Signal "0"-30 V DC ... 5 V DC
Input Voltage Range Signal "1"11 V DC ... 30.2 V DC
Nominal Input Voltage UIN24 V DC
Nominal input current to UINTyp. 3.7 mA (with 24 V DC)
max. 4.3 mA (with 30.2 V DC)
Inlet Filter Time1.5 ms
3 ms (Default)
5 ms
15 ms
Protection CircuitOverload protection, short-circuit protection of sensor power
IO-Link
Number of ports1
Connection typeM12 plug-in connector, A-coded
Connection technology3 conductors
Port ModelClass A
SpecificationV1.1.2
Polarity reversal protectionYes
Transmission speed230.4 kBit/s (COM3)
Cycle Time≥ 4 ms
Updating Process Data≥ 4 ms
Number of process data64 Bit (Input and Output Data)

Output Data
Digital
Denomination OutputSecure Digital Outputs
Connection typeM12 plug-in connector (A-coded)
Connection technology2 conductors
Number of outputs4 (with 2-channel assignment, +/- switching)
4 (with 1-channel assignment, + switching)
Protection CircuitOverload protection, outputs short-circuit protection
Output voltageUto- 1.4 V
Output currentmax. 2 A (per channel)
max. 2 A (per output)
max. 6 A (Current sum of all outputs, please note the indications in the user manual.)
Maximum Output Current Per Channel2 A
Nominal Output Voltage24 V DC (Voltage Us)
Min. Charge2.4 kΩ (10 mA at 24 V DC)
Output voltage in disconnected state< 5 V (in Low state))
Output current in disconnected state2 mA (Leakage current in "Low" state)
Delay Timemax. 128 s (parameterizable)
Permissible cable lengthmax. 50 m
Number of manoeuvresmax. 1 Hz
Resistance to return voltage, against short impulsesNo

Item Properties
ConstructionStand-Alone
Product TypeI/O Component
Product FamilyAxioline E
Position for mountingdiscretionary
applicationFunctional safety
Operating Mode4-word process data service
Insulation Properties
Degree of pollution4

Electrical Properties
Power: IO-Link
DenominationIO-Link Port Power (L+)
Nominal Peripheral Supply Voltage24 V DC (Made available via the IO-Link interface of the IO-Link master.)
Supply voltage19.2 V DC ... 30.2 V DC (incl. all tolerances, incl. ripple)
Nominal current per deviceapprox. 15 mA
Permissible cable lengthmax. 20 m
Protection CircuitProt. Against polarity reversal
Power: Modular electronics and sensors
DenominationPower supply of modular electronics and sensors (Us)
Connection typeM12 connector (L-coded)
Number of poles2
Supply voltage24 V DC
Supply voltage19.2 V DC ... 30.2 V DC (incl. all tolerances, incl. ripple)
Current absorption67 mA (Without Sensors)
Fuse protectionmax. 8 A (slow)
Power: Actuators
DenominationActuator Power (Uto)
Connection typeM12 connector (L-coded)
Number of poles2
Supply voltage24 V DC
Supply voltage19.2 V DC ... 30.2 V DC (incl. all tolerances, incl. ripple)
Current absorption52 A (without actuators)
Fuse protectionmax. 8 A (slow)

Connection data
Connection typeM12 plug-in connector
Note about the connection typeaccording to IEC 61076-2-101, M12 connection technology

Environmental and life-life conditions
Environmental conditions
Ambient Temperature (Service)-25 °C ... 60°C (Mounting Position: Discretionary)
Protection IndexIP65/IP67 (according to DIN EN 60529:1989 + A1:1999 + A2:2013)
ObservationResistant to hazardous gas for operation (sulfur dioxide (SO)2), hydrogen sulfide (H2S))
Air Pressure (Service)70 kPa ... 108 kPa (up to 3000 m above NN)
Air Pressure (Storage/Transport)66 kPa ... 108 kPa (up to 3500 m above NN)
Ambient Temperature (Storage/Transport)-40 °C ... 85 °C
Permissible air humidity (storage/transport)75% (non-condensing)

Standards & Specifications
Kind of protectionIII (IEC 61140, EN 61140, VDE 0140-1)
Creepage Lines and Air Isolation Distances
Leak lines and air gapsaccording to IEC 60664-1

assembly
Position for mountingdiscretionary

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.