AXL E IOL DI8 M12 6P 2702658 PHOENIX CONTACT Distributed I/O device
AXL E IOL DI8 M12 6P
2702658
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - digital I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A distributed I/O device from Phoenix Contact, identified by part number AXL E IOL DI8 M12 6P, collects decentralized sensor and actuator data in industrial machinery and routes it back to the central controller via network communication. Decentralized input blocks minimize cabinet wiring and improve signal acquisition efficiency across large automation layouts. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 8
- Number of digital outputs (EF001993): 0
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Input current at signal 1 (EF001428): 0.0024 mA
- Permitted voltage at input (EF007554): -3 V
- Type of voltage (input voltage) (EF003033): DC
- Short-circuit protection, outputs available (EF003203): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces parallel (EF003026): 0
More info
▲Key Commercial Data
| Orderkey | 2702658 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626279671 |
| Weight per Piece (excluding packing) | 299.000 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 60 mm |
| Height | 141 mm |
| Depth | 20 mm |
| Note on dimensions | The height is 170 mm including fixing clips. The depth is 30 mm including the connector. |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Permissible humidity (storage/transport) | 5 % ... 95 % |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP65/IP67 |
Digital inputs
| Description of the input | EN 61131-2 types 1 and 3 |
|---|---|
| Connection method | M12 connector |
| Connection technology | 4-wire |
| Number of inputs | 8 |
| Type of protection | Overload protection, short-circuit protection of sensor supply |
| Polarity reversal protection of the inputs | |
| Input filter time | 1 ms |
| Input voltage range "0" signal | -3 V ... 5 V DC |
| Input voltage range "1" signal | 11 V DC ... 30 V DC |
| Nominal input current at UIN | typ. 2.4 mA |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|