PHOENIX CONTACT AXL E IOL DI16 M12 6P AXL E IOL DI16 M12 6P 2702660 PHOENIX CONTACT Axioline E digital input device via IO-Link in plastic housing.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL E IOL DI16 M12 6P 2702660 PHOENIX CONTACT Axioline E digital input device via IO-Link in plastic housing..

AXL E IOL DI16 M12 6P

2702660

PHOENIX CONTACT

1 Pcs.

Axioline E digital input device via IO-Link in plastic housing with an IO-Link A-port and 16 inputs, 24 V DC, 4-conductor technology, M12 fast connection technology

Automation > Fieldbus, decentr. periphery - digital I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact Axioline E digital input device via IO-Link in plastic housing, designated by part number AXL E IOL DI16 M12 6P, collects discrete sensor signals directly from decentralized machine environments. These modules utilize IO-Link communication to streamline wiring and feed binary status data back to the primary controller.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Voltage type (supply voltage) (EF002991): DC
  • Number of digital inputs (EF001992): 16
  • Number of digital outputs (EF001993): 0
  • Digital inputs configurable (EF008516): No
  • Digital outputs configurable (EF008520): No
  • Input current at signal 1 (EF001428): 0.0024 mA
  • Permitted voltage at input (EF007554): -3 V
  • Type of voltage (input voltage) (EF003033): DC
  • Short-circuit protection, outputs available (EF003203): No
  • Number of HW-interfaces industrial Ethernet (EF003020): 0
  • Number of interfaces PROFINET (EF006932): 0
  • Number of HW-interfaces RS-232 (EF003021): 0
  • Number of HW-interfaces RS-422 (EF003022): 0
  • Number of HW-interfaces RS-485 (EF003023): 0
  • Number of HW-interfaces serial TTY (EF003024): 0
  • Number of HW-interfaces parallel (EF003026): 0

More info

▲

Key Commercial Data

Orderkey2702660
Packing unit1 pc
Catalog pagePage 180 (C-6-2019)
GTIN4055626280103
Weight per Piece (excluding packing)300.000 g
Custom tariff number85176200
Country of originDE (Germany)

Drawings



Connection diagram

Dimensional drawing



Back to top

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Dimensional drawing
Width60 mm
Height141 mm
Depth20 mm
Note on dimensionsThe height is 170 mm including fixing clips. The depth is 30 mm including the connector.
Back to top

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C
Permissible humidity (operation)5 % ... 95 %
Permissible humidity (storage/transport)5 % ... 95 %
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP65/IP67
Back to top

Digital inputs

Description of the inputEN 61131-2 types 1 and 3
Connection methodM12 connector
Connection technology4-wire
Number of inputs16
Protective circuitOverload protection, short-circuit protection of sensor supply
Polarity reversal protection of the inputs
Nominal input voltage UIN24 V DC
Nominal input current at UINtyp. 2.4 mA
Input filter time1 ms
Cable lengthmax. 30 m (To the sensor)
Input voltage range "0" signal-3 V ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Back to top

General

Housing materialPocan®
Mounting typeWall mounting
Coloranthracite grey RAL 7016
Net weight295.6 g
Back to top

Electrical isolation

Test section24 V supply/FE 500 V AC 50 Hz 1 min.
Back to top

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)
Back to top

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 6.027242600
eCl@ss 7.027242604
eCl@ss 8.027242604
eCl@ss 9.027242604
Back to top

ETIM

ETIM 5.0EC001599
ETIM 6.0EC001599
ETIM 7.0EC001599
Back to top

UNSPSC

UNSPSC 13.232151602
UNSPSC 18.032151602
UNSPSC 19.032151602
UNSPSC 20.032151602
UNSPSC 21.032151602
Back to top

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.