View larger
AXL E IOL AO1 I M12 S 2700351 PHOENIX CONTACT Distributed I/O device
AXL E IOL AO1 I M12 S
2700351
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Distributed I/O device carrying the Phoenix Contact part number AXL E IOL AO1 I M12 S 2700351 connects remote field instrumentation back to a central controller via industrial communication protocols. This hardware minimizes cabinet wiring requirements by placing data collection points directly on the machine frame. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Note on application Note on application: Only for industrial use
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Product type: Interface converter
- Product family: Axioline E
- Type: Stand-Alone
- Type: straight
- Diagnostics messages: Short circuit Message in the diagnostic code (in the IB IL format)
- Data management status Article revision: 01
- Insulation characteristics Pollution degree: 2
- Supply: IO-Link Nominal voltage for I/O supply: 24 V DC (This supply voltage is provided via the IO-Link interface of the IO-Link master.)
- Nominal current for every IO-Link port: max. 100 mA
- Current consumption: typ. 16.5 mA ±15 % (at 24 V DC)
- Protective circuit: Reverse polarity protection
- IO-Link Number of ports: 1
- Connection method: M12 connector, A-coded
- Connection technology: 3-conductor
More info
▲| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Interface converter |
| Product family | Axioline E |
| Type | Stand-Alone |
| Axioline E | |
| Type | straight |
| Diagnostics messages | Short circuit Message in the diagnostic code (in the IB IL format) |
| Configuration invalid Message in the diagnostic code (in the IB IL format) | |
| Module faulty Message in the diagnostic code (in the IB IL format) | |
| Data management status | |
| Article revision | 01 |
| Insulation characteristics | |
| Pollution degree | 2 |
| Supply: IO-Link | |
| Nominal voltage for I/O supply | 24 V DC (This supply voltage is provided via the IO-Link interface of the IO-Link master.) |
| Nominal current for every IO-Link port | max. 100 mA |
| Current consumption | typ. 16.5 mA ±15 % (at 24 V DC) |
| max. 135 mA | |
| Protective circuit | Reverse polarity protection |
| Short-circuit protection | |
| Overload protection | |
| IO-Link | |
| Number of ports | 1 |
| Connection method | M12 connector, A-coded |
| Connection technology | 3-conductor |
| Specification | V1.1.1 |
| Reverse polarity protection | yes |
| Cycle Time | min. 2 ms |
| Process data update | 2 ms |
| Amount of process data | 16 bit (Input data) |
| 16 bit (Output data) | |
| Analog: | |
| Output name | Analog output |
| Connection method | M12 connector, A-coded |
| Connection technology | 3-conductor |
| Number of outputs | 1 (current) |
| D/A converter resolution | 12 bit |
| Data formats | IB IL, S7-compatible |
| Current output signal | 4 mA ... 20 mA |
| Load/output load current output | max. 500 Ω |
| Permissible cable length | max. 30 m (Shielded cable) |
| Diagnostic messages | |
| Diagnostics | Short circuit |
| Message | Message in the diagnostic code (in the IB IL format) |
| Diagnostic messages | |
| Diagnostics | Configuration invalid |
| Message | Message in the diagnostic code (in the IB IL format) |
| Diagnostic messages | |
| Diagnostics | Module faulty |
| Message | Message in the diagnostic code (in the IB IL format) |
| Dimensional drawing | |
| Width | 16.6 mm |
| Height | 29 mm |
| Depth | 79.5 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Degree of protection | IP65/IP67 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Permissible humidity (storage/transport) | 5 % ... 95 % |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |