View larger
AXL E ETH IOL8 DI4 M12 6P 2701536 PHOENIX CONTACT Distributed I/O device
AXL E ETH IOL8 DI4 M12 6P
2701536
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - digital I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Operating as a distributed I/O device, the Phoenix Contact AXL E ETH IOL8 DI4 M12 6P connects field sensors and industrial Ethernet architectures on automated production floors. Decentralized I/O blocks are utilized to simplify machine wiring topologies by gathering sensor data directly near the application point.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 4
- Number of digital outputs (EF001993): 0
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Input current at signal 1 (EF001428): 0.003 mA
- Permitted voltage at input (EF007554): -0.3 V
- Type of voltage (input voltage) (EF003033): DC
- Short-circuit protection, outputs available (EF003203): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces parallel (EF003026): 0
More info
▲Key Commercial Data
| Orderkey | 2701536 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 197 (C-6-2017) |
| GTIN | 4046356763844 |
| Weight per Piece (excluding packing) | 554.300 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 60 mm |
| Height | 185 mm |
| Depth | 30.5 mm |
| Note on dimensions | The height is 212 mm including fixing clips. |
| Drill hole spacing | 198.5 mm |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Permissible humidity (storage/transport) | 5 % ... 95 % |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP65/IP67 |
Interfaces
| Designation | Ethernet |
|---|---|
| No. of channels | 2 |
| Connection method | M12 fast connection technology |
| Note on the connection method | D-coded |
| Designation connection point | Copper cable |
| Transmission speed | 10/100 Mbps (with auto negotiation) |
| Number of positions | 4 |
System limits of the bus coupler
| Designation | Modbus/TCP |
|---|---|
| Equipment type | Modbus slave (server) |
| System-specific protocols | Modbus protocols Modbus/TCP |
| Protocols supported | SNMP v1 |
| HTTP | |
| TFTP | |
| FTP | |
| BootP | |
| DHCP | |
| Specification | Modbus application protocol V1.1b |
Supply
| Designation | Module electronics and sensors (US) |
|---|---|
| Connection method | M12 connector (T-coded) |
| Number of positions | 4 |
| Supply voltage | 24 V DC |
| Nominal supply voltage range | 19.5 V DC ... 31.2 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 180 mA ±15 % (at 24 V DC) |
| Designation | Actuators (UA) |
| Connection method | M12 connector (T-coded) |
| Number of positions | 4 |
| Supply voltage | 24 V DC |
| Nominal supply voltage range | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 28 mA ±15 % (at 24 V DC) |
Digital inputs
| Input name | Digital inputs at pin 2 for type A ports |
|---|---|
| Description of the input | IEC 61131-2 type 1 |
| Connection method | M12 connector, X01 ... X04 have double occupancy |
| Connection technology | 3-wire |
| Number of inputs | 4 |
| Type of protection | Overload protection, short-circuit protection of sensor supply |
| Input filter time | < 1000 µs |
| Input voltage range "0" signal | -0.3 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Input frequency | 0.5 kHz |
| Nominal input current at UIN | typ. 3 mA |
| Description of the input | IO-Link ports in digital input (DI) mode |
| Connection method | M12 connector, X01 ... X04 have double occupancy |
| Connection technology | 3-wire |
| Number of inputs | max. 8 (EN 61131-2 type 1) |
| Nominal input voltage UIN | 24 V DC |
| Input voltage range "0" signal | -0.3 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Nominal input current | typ. 3 mA |
| Sensor current per channel | max. 200 mA (from L+/L-) |
| Total sensor current | max. 1.6 A (from L+/L-) |
| Input filter time | < 1000 µs |
| Input frequency | 0.5 kHz |
| Type of protection | Overload protection |
| Short-circuit protection for the sensor supply |
Digital outputs
| Output description | IO-Link ports in digital output (DO) mode |
|---|---|
| Connection method | M12 connector, X01 ... X04 have double occupancy |
| Connection technology | 3-wire |
| Number of outputs | max. 8 |
| Nominal output voltage | 24 V DC |
| Maximum output current per channel | 150 mA |
| Maximum output current per device | 1.2 A |
| Nominal load, ohmic | 3.6 W (160 Ω, at nominal load) |
| Nominal load, inductive | 3.6 VA (0.8 H, 160 Ω, at nominal load) |
| Signal delay | max. 150 µs (when switched on) |
| max. 200 µs (when switched off) | |
| Switching rate | 1 per second, maximum (at nominal inductive load) |
| Limitation of the voltage induced on circuit interruption | -15 V DC |
| Output voltage when switched off | max. 1 V |
| Output current when switched off | max. 300 µA |
| Type of protection | Overload protection |
| Short-circuit protection | |
| Behavior with overload | Shutdown with automatic restart |
Electrical isolation
| Test section | 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min. |
|---|---|
| 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min. | |
| 24 V supply (communications power and sensor supply, IO-Link ports)/FE 500 V AC 50 Hz 1 min. | |
| Bus connection (Ethernet 1)/FE 500 V AC 50 Hz 1 min. | |
| Bus connection (Ethernet 2)/FE 500 V AC 50 Hz 1 min. | |
| Bus connection (Ethernet 1)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min. | |
| 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports) 500 V AC 50 Hz 1 min. | |
| 24 V supply (actuator supply)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min. | |
| 24 V supply (actuator supply)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min. | |
| 24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |