PHOENIX CONTACT AXL F CNT2 INC2 XC 1F AXL F CNT2 INC2 XC 1F 2701239 PHOENIX CONTACT Special function module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AXL F CNT2 INC2 XC 1F 2701239 PHOENIX CONTACT Special function module

AXL F CNT2 INC2 XC 1F

2701239

PHOENIX CONTACT

1 Pcs.

Special function module AxiolineF, Function module, Counter input for 24 V signals:2, Incremental value transmitter inputs:2, Symmetrical and asymmetric transmitters, Digital inputs:8, 24 VDC, Digital outputs:2, 24 VDC, Extreme Condition variant, transmission speed on the local bus:100 MBit/s, protection index:IP20, including bus socket module and AxiolineF connectors

Automation > Fieldbus, decentr. periphery - function-/technology module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact AXL F CNT2 INC2 XC 1F is a special function module engineered for demanding industrial control systems requiring advanced counting and positioning tasks. Special function modules expand modular I/O node capabilities, allowing controllers to handle dedicated measurement and control algorithms locally. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage DC (EF007534): 19.2 V
  • Number of functions (EF003244): 1
  • Number of HW-interfaces industrial Ethernet (EF003020): 0
  • Number of interfaces PROFINET (EF006932): 0
  • Number of HW-interfaces RS-232 (EF003021): 0
  • Number of HW-interfaces RS-422 (EF003022): 0
  • Number of HW-interfaces RS-485 (EF003023): 0
  • Number of HW-interfaces serial TTY (EF003024): 0
  • Number of HW-interfaces parallel (EF003026): 0
  • Number of HW-interfaces wireless (EF006933): 0
  • Number of HW-interfaces USB (EF003025): 0
  • Number of HW-interfaces other (EF003027): 0
  • With optical interface (EF003028): No
  • Supporting protocol for EtherCAT (EF017564): No
  • Supporting protocol for TCP/IP (EF003050): No
  • Supporting protocol for PROFIBUS (EF003052): Yes

More info

▲

Key Commercial Data

Orderkey2701239
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 121 (C-6-2017)
GTIN4046356730082
Weight per Piece (excluding packing)233.900 g
Custom tariff number85389091
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Dimensional drawing
Width53.6 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Mounting typeDIN rail
Net weight233.9 g
Note on weight specificationswith connectors and bus base module
Diagnostics messagesShort-circuit / overload of the digital outputs Yes
Error at the symmetrical incremental encoder Yes

Interfaces

DesignationAxioline F local bus
No. of channels2
Connection methodBus base module
Transmission speed100 Mbps

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptiontyp. 100 mA
max. 120 mA
Power consumptiontyp. 0.5 W
max. 0.6 W
DesignationSupply voltage input UI
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC including all tolerances, including ripple
Current consumptionmax. 2.5 A (dependent on the encoder or sensor type used and the load on the digital output.)
Power consumptionmax. 60 W (of which 1.6 W internal losses)
Type of protectionSurge protection of the supply voltage
Polarity reversal protection of the supply voltage
Protectionmax. 8 A (polarity reversal protection up to 5 A)

Counter inputs

Input nameCounter input for 24 V signals
Number of inputs2 (S1, S2)
Description of the inputEN 61131-2, type 3
Connection methodPush-in connection
Input voltage24 V DC
Input voltage range "0" signal-3 V DC ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Input frequencymax. 300 kHz (1 channel wired)
max. 100 kHz (More than one channel wired or Z signal monitoring via the firmware)
Input current2.5 mA (per channel)
Resolution32 bits
Permissible cable length to the sensor30 m

Encoder inputs

Input nameIncremental encoder inputs
Number of inputs2 (A1, /A1, B1, /B1, Z1, /Z1; A2, /A2, B2, /B2, Z2, /Z2)
Connection methodPush-in connection
Encoder signalsSymmetrical and asymmetrical encoders
Cable length30 m

Encoder data

Number of 5 V encoder supplies2 (UE1, UE2)
Nominal output voltage5 V DC
Voltage range5 V DC ... 5.5 V DC
Current carrying capacitymax. 250 mA
Type of protectionShort-circuit protection
Number of 24 V encoder supplies2 (US1, US2)
Nominal output voltage24 V DC
Voltage range19.2 V DC ... 30 V DC
Current carrying capacitytyp. 500 mA
Type of protectionShort-circuit protection
DesignationSymmetrical incremental encoders
Encoder types that can be connectedmax. 2 (A, /A, B, /B, (Z, /Z))
Type of connection of signalsPush-in connection
Encoder supply voltage5 V DC
24 V DC
Signal voltage levelDifferential signal (signal – inverted signal) ±0.5 V, minimum; ±6 V, maximum
Common mode voltage range signal - ground-10 V ... 13.2 V
Input frequencymax. 300 kHz (1 channel wired)
max. 100 kHz (More than one channel wired or Z signal monitoring via the firmware)
DesignationAsymmetrical incremental encoders
Encoder types that can be connectedmax. 2 (A, B, (Z))
Type of connection of signalsPush-in connection
Signal voltage levelLow ≤ 2.5 V, high ≥ 3.5 V (up to 27 V, maximum)
Input frequencymax. 300 kHz (1 channel wired)
max. 100 kHz (More than one channel wired or Z signal monitoring via the firmware)

Digital inputs

Input nameDigital inputs
Description of the inputEN 61131-2, type 3
Connection methodPush-in connection
Connection technology1-wire (optionally 2, 3-wire)
Number of inputs8 (CNT: G1, G2, Dir1, Dir2; INC: Ref1, Ref2, L1, L2)
Input voltage range "0" signal-3 V DC ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Nominal input current at UIN2.5 mA (per channel)

Digital outputs

Output nameDigital outputs
Connection methodPush-in connection
Connection technology1-wire
Number of outputs2 (Out1, Out2)
Type of protectionShort-circuit protection, overload protection of the outputs
Output voltage24 V DC
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Nominal load, inductivemax. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lampmax. 12 W (at nominal voltage)
Nominal load, ohmicmax. 12 W (48 Ω, with nominal voltage)

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.