Providing robust control capabilities for higher-voltage loads, the AXL F DO4/3 AC 1F 2702068 PHOENIX CONTACT I/O module interfaces controller logic with field devices running on alternating current. Such output modules are deployed within modular automation stations to govern higher voltage actuators safely and reliably.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 12 V
- Supply voltage AC 60 Hz (EF007533): 12 V
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 0
- Number of digital outputs (EF001993): 4
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Type of voltage (input voltage) (EF003033): DC
- Output current (EF003202): 2 A
- Permitted voltage at output (EF007553): 230 V
- Short-circuit protection, outputs available (EF003203): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
More info
▲Key Commercial Data
| Orderkey | 2702068 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 110 (C-6-2017) |
| GTIN | 4046356933087 |
| Weight per Piece (excluding packing) | 239.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C (max. 2 A/channel for wall mounting on horizontal DIN rail; max. 1 A/channel for any mounting position) |
|---|---|
| -25 °C ... 50 °C (max. 2 A/channel for any mounting position) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Connection data
| Designation | Axioline F connector |
|---|---|
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 239 g |
| Note on weight specifications | with connectors and bus base module |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | max. 120 mA |
| Power consumption | max. 600 mW |
| Designation | Supply for digital output modules (UO) |
| Supply voltage | 230 V AC |
| Supply voltage range | 12 V AC ... 253 V AC (including all tolerances, including ripple, 50 ... 60 Hz) |
| Current consumption | max. 8 A (provide external protection) |
| Power consumption | max. 2024 VA (of which 8 VA internal losses) |
| Type of protection | Surge protection of the supply voltage |
| Protection | max. 8 A |
Digital outputs
| Output name | Digital outputs |
|---|---|
| Connection method | Push-in connection |
| Connection technology | 3-wire |
| Number of outputs | 4 (Triac outputs with zero voltage switch) |
| Type of protection | External protection required |
| Output voltage | 230 V AC |
| Nominal output voltage | 230 V AC |
| Maximum output current per channel | 2 A AC |
| Maximum output current per module | 8 A AC (provide external protection) |
| Nominal load, ohmic | max. 460 W (at nominal voltage) |
Electrical isolation
| Test section | I/Os / logic 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201) |
|---|---|
| I/Os / logic 5 kV Pulse test voltage according to EN 61850/IEC 61850 | |
| I/O / functional earth ground 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201) | |
| I/O / functional earth ground 5 kV Pulse test voltage according to EN 61850/IEC 61850 | |
| I/O area AC / PE 4 kV Rated surge voltage (basic insulation according to EN 61010-2-201/IEC 61010-2-201) |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Developed according to standard | IEC 61850-3 Immunity to magnetic fields, EN 61000-4-8/IEC 61000-4-8 300 A/m continuous, 1000 A/m for 1 s |
| IEC 61850-3 Immunity to attenuated oscillating magnetic fields, EN 61000-4-10/IEC 61000-4-10 100 A/m | |
| IEC 61850-3 Immunity to conducted common-mode interference, EN 61000-4-16/IEC 61000-4-16 30 V continuous, 300 V for 1 s | |
| IEC 61850-3 Attenuated oscillating waves, EN 61000-4-18/IEC 61000-4-18 1 kV symmetrical, 2.5 kV asymmetrical |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |