View larger
AXL F DI8/3 DO8/3 2H 2702071 PHOENIX CONTACT I/O module
AXL F DI8/3 DO8/3 2H
2702071
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - digital I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Combining both signal collection and actuation control, the Phoenix Contact AXL F DI8/3 DO8/3 2H I/O module manages mixed binary signals within automated control loops. Such multi-functional terminal units optimize panel space by handling both input sensing and output switching in one footprint. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 8
- Number of digital outputs (EF001993): 8
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Input current at signal 1 (EF001428): 0.0024 mA
- Permitted voltage at input (EF007554): -3 V
- Type of voltage (input voltage) (EF003033): DC
- Output current (EF003202): 0.5 A
- Permitted voltage at output (EF007553): 24 V
- Short-circuit protection, outputs available (EF003203): Yes
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
More info
▲Key Commercial Data
| Orderkey | 2702071 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 113 (C-6-2017) |
| GTIN | 4046356933094 |
| Weight per Piece (excluding packing) | 159.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 35 mm |
| Height | 129.9 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Connection data
| Designation | Axioline F connector |
|---|---|
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 159 g |
| Note on weight specifications | with connectors and bus base module |
| Diagnostics messages | I/O supply failure Yes |
| Short-circuit / overload of the digital outputs Yes |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | max. 120 mA |
| Power consumption | max. 600 mW |
| Designation | Supply for digital input and output modules (UIO) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | max. 6 A (provide external protection) |
| Power consumption | max. 180 W (of which 1.24 W internal losses) |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage | |
| Protection | max. 8 A (polarity reversal protection up to 5 A) |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | EN 61131-2 types 1 and 3 |
| Connection method | Push-in connection |
| Connection technology | 3-wire |
| Number of inputs | 8 |
| Type of protection | Polarity reversal protection of the inputs |
| Input filter time | 3000 µs (default) |
| Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 11 V DC ... 30 V DC |
| Nominal input current at UIN | 2.4 mA |
Digital outputs
| Output name | Digital outputs |
|---|---|
| Connection method | Push-in connection |
| Connection technology | 3-wire |
| Number of outputs | 8 |
| Type of protection | Short-circuit protection, overload protection of the outputs |
| Output voltage | 24 V DC |
| Nominal output voltage | 24 V DC |
| Maximum output current per channel | 500 mA |
| Maximum output current per module | 8 A (provide external protection) |
| Nominal load, inductive | max. 12 VA (1.2 H, 48 Ω, with nominal voltage) |
| Nominal load, lamp | max. 12 W (at nominal voltage) |
| Nominal load, ohmic | max. 12 W (48 Ω, with nominal voltage) |
Electrical isolation
| Test section | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |