View larger
AXL F BK S3 2701686 PHOENIX CONTACT Bus coupler
AXL F BK S3
2701686
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Bus coupler, cataloged as the Phoenix Contact AXL F BK S3, acts as a primary network node that connects Axioline F I/O systems to high-performance Sercos automation networks. Sercos bus couplers deliver rapid cycle times and synchronized motion control capabilities for sophisticated industrial machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Width: 45 mm
- Height: 126.1 mm
- Depth: 74 mm
- Note on dimensions: The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
- Note on application Note on application: Only for industrial use
- Sercos Number of interfaces: 2
- Connection method: RJ45 jack
- Note on the connection method: Auto negotiation and autocrossing
- Transmission speed: 100 Mbps (full duplex)
- Transmission physics: Ethernet in RJ45 twisted pair
- Axioline F local bus Number of interfaces: 1
- Connection method: Bus base module
- Transmission speed: 100 Mbps
- Service Number of interfaces: 1
- Connection method: USB type C (from HW 05)
- Sercos Equipment type: Sercos slave
More info
▲| Dimensional drawing | |
| Width | 45 mm |
| Height | 126.1 mm |
| Depth | 74 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Note on application | |
| Note on application | Only for industrial use |
| Sercos | |
| Number of interfaces | 2 |
| Connection method | RJ45 jack |
| Note on the connection method | Auto negotiation and autocrossing |
| Transmission speed | 100 Mbps (full duplex) |
| Transmission physics | Ethernet in RJ45 twisted pair |
| Axioline F local bus | |
| Number of interfaces | 1 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Service | |
| Number of interfaces | 1 |
| Connection method | USB type C (from HW 05) |
| Micro USB type B (up to HW 04) | |
| Sercos | |
| Equipment type | Sercos slave |
| System-specific protocols | Sercos protocols Sercos |
| Specification | Sercos specification 1.31 |
| System limits | |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 63 |
| Product type | I/O component |
| Product family | Axioline F |
| Type | block modular |
| Mounting position | any (observe temperature derating) |
| Scope of delivery | including bus base module and Axioline F connector |
| Data management status | |
| Article revision | 17 |
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Maximum power dissipation for nominal condition | 3.7 W |
| Potentials: Communications power ULfeed-in (the supply of the Axioline F local bus UBusis generated from UL) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 570 mA (2.0 A at UBus, UL= 24 V, up to HW 04) |
| max. 670 mA (2.5 A at UBus, UL= 24 V, from HW 05) | |
| Protective circuit | Surge protection; electronic |
| Reverse polarity protection; electronic | |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Power supply unit | max. 2 A (up to HW 04) |
| max. 2.5 A (from HW 05) | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Ethernet interface 1 / Ethernet interface 2 | 1500 V AC, 50 Hz, 1 min. |
| Test voltage: Ethernet interface 1 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min. |
| Test voltage: Ethernet interface 2 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min. |
| Test voltage: Ethernet interface 1 / functional ground | 1500 V AC, 50 Hz, 1 min. |
| Test voltage: Ethernet interface 2 / functional ground | 1500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V communications voltage (UL) feed-in / functional ground | 500 V AC, 50 Hz, 1 min. |
| Connection technology | |
| Connection name | Axioline F connector |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Axioline F connector | |
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail) |
| -25 °C ... 55 °C (Mounting position: any) | |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |
| Mounting position | any (observe temperature derating) |