View larger
AXL F BK PB 2688530 PHOENIX CONTACT Bus coupler
AXL F BK PB
2688530
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact AXL F BK PB bus coupler acts as a vital communication node that links modular I/O arrays to industrial fieldbus networks. By bridging the gap between field devices and higher-level controllers, units of this kind facilitate efficient real-time data exchange in automated factory environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for EtherNet/IP (EF007521): No
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- IO link master (EF007298): No
- System accessory (EF004118): Yes
- Degree of protection (IP) (EF005474): IP20
- With potential separation (EF003272): No
- Suitable for rail mounting (EF003972): Yes
- Wall mounting/direct mounting (EF007020): No
- Front built-in possible (EF007016): No
- Rack-assembly possible (EF007018): No
- Suitable for safety functions (EF001597): No
More info
▲Key Commercial Data
| Orderkey | 2688530 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 104 (C-6-2017) |
| GTIN | 4046356712903 |
| Weight per Piece (excluding packing) | 175.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 45 mm |
| Height | 125.9 mm |
| Depth | 74 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail) |
|---|---|
| -25 °C ... 55 °C (Mounting position: any) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Connection data
| Designation | Axioline F connector |
|---|---|
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 175 g |
| Note on weight specifications | with connector and bus base module |
| Diagnostics messages | Diagnostic alarms |
Interfaces
| Designation | PROFIBUS DP |
|---|---|
| No. of channels | 1 |
| Connection method | D-SUB-9 female connector |
| Transmission speed | 9.6 kbps ... 12 Mbps |
| Number of positions | 9 |
| Designation | Axioline F local bus |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Designation | Service |
| Connection method | Micro USB type B |
System limits of the bus coupler
| Designation | System limits of the bus coupler |
|---|---|
| Amount of process data | max. 488 Byte (per station) |
| max. 244 Byte (Input) | |
| max. 244 Byte (Output) | |
| Number of parameter data | max. 244 Byte |
| Number of configuration data | max. 244 Byte |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 63 |
Axioline potentials
| Designation | Communications power ULfeed-in (the supply of the Axioline F local bus UBusis generated from UL) |
|---|---|
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | max. 567 mA (with 2 A at UBusfor the I/Os and UL= 24 V) |
| Power consumption | max. 13.7 W (with 2 A load at UBusfor the I/Os) |
| Designation | Axioline F local bus supply (UBus) |
| Supply voltage | 5 V DC (via bus base module) |
| Power supply unit | 2 A |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |