View larger
AXL F AO8 XC 1F 2701237 PHOENIX CONTACT I/O module
AXL F AO8 XC 1F
2701237
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact I/O module delivers multi-channel analog output control for industrial automation networks, regulating drives, valves, and proportional devices with high precision. Such output expansion modules are deployed in complex processing plants to execute control loop commands sent from central controllers.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Output, current (EF003212): Yes
- Output, voltage (EF003213): Yes
- Output signal configurable (EF003214): Yes
- Resolution of the analogue outputs (EF003577): 16 Bit
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 8
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): Yes
More info
▲Key Commercial Data
| Orderkey | 2701237 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 117 (C-6-2017) |
| GTIN | 4046356729857 |
| Weight per Piece (excluding packing) | 260.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C (Standard) |
|---|---|
| -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 260 g |
| Note on weight specifications | with connectors and bus base module |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | typ. 105 mA |
| max. 130 mA | |
| Power consumption | typ. 0.525 W |
| max. 0.65 W | |
| Designation | Supply for analog modules (UA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 110 mA (8 voltage channels, 10 V output) |
| max. 235 mA (8 current channels, 20 mA output) | |
| Power consumption | max. 5.64 W (8 current channels, 20 mA output) |
| typ. 1.725 W (to UBusand UA;power input; no load, output 0 V) | |
| max. 6.29 W (to UBusand UA; 8 current channels, output 20 mA) | |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage | |
| Transient protection supply voltage |
Analog outputs
| Number of outputs | 8 |
|---|---|
| Connection method | Push-in connection |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded, twisted pair |
| Output name | Analog outputs |
| D/A conversion time | 5 µs |
| D/A resolution | 16 bit |
| Type of protection | Short-circuit and overload protection |
| Transient protection | |
| Protective circuit/component | electronic |
| Suppressor diode | |
| Data formats | IB IL, S7-compatible |
| Representation of output values | 16 bits (15 bits + sign) |
| Process data update | 300 µs |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| -20 mA ... 20 mA | |
| Load/output load current output | to 500 Ω |
| Voltage output signal | 0 V ... 5 V |
| -5 V ... 5 V | |
| 0 V ... 10 V | |
| -10 V ... 10 V | |
| Load/output load voltage output | > 2 kΩ |
| Precision | typ. 0.1 % (of output range final value) |
| Permissible cable length | max. 250 m |
Electrical isolation
| Test section | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply (logic)/analog outputs 500 V AC 50 Hz 1 min. | |
| 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O)/analog outputs 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. | |
| Analog outputs/functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |