AXL F AO4 XC 1H 2702153 PHOENIX CONTACT I/O module
AXL F AO4 XC 1H
2702153
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact model AXL F AO4 XC 1H (referenced as AXL F AO4 XC 1H 2702153 PHOENIX CONTACT I/O module) acts as an output interface module designed to convert digital controller values into standard analog control signals for actuators. It integrates directly into modular industrial bus systems to drive variable devices in demanding manufacturing environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Width: 35 mm
- Height: 126.1 mm
- Depth: 54 mm
- Note on dimensions: The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
- Note on application Note on application: Only for industrial use
- Axioline F local bus Number of interfaces: 2
- Connection method: Bus base module
- Transmission speed: 100 Mbps
- Module Input address area: 8 Byte
- Output address area: 8 Byte
- Required parameter data: 14 Byte
- Required configuration data: 7 Byte
- Analog: Output name: Analog outputs
- Connection method: Push-in connection
- Connection technology: 2-conductor
- Note regarding the connection technology: shielded, twisted pair
More info
▲| Dimensional drawing | |
| Width | 35 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Note on application | |
| Note on application | Only for industrial use |
| Axioline F local bus | |
| Number of interfaces | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Module | |
| Input address area | 8 Byte |
| Output address area | 8 Byte |
| Required parameter data | 14 Byte |
| Required configuration data | 7 Byte |
| Analog: | |
| Output name | Analog outputs |
| Connection method | Push-in connection |
| Connection technology | 2-conductor |
| Note regarding the connection technology | shielded, twisted pair |
| Number of outputs | 4 |
| D/A converter resolution | 16 bit |
| Protective circuit | Short-circuit and overload protection; electronic |
| Transient protection; Suppressor diode | |
| Data formats | IB IL, S7-compatible |
| Representation of output values | 16 bits (15 bits + sign) |
| Process data update | 140 µs |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Load/output load current output | ≤ 500 Ω |
| Voltage output signal | 0 V ... 5 V |
| -5 V ... 5 V | |
| 0 V ... 10 V | |
| -10 V ... 10 V | |
| Load/output load voltage output | ≥ 1 kΩ |
| Product type | I/O component |
| Product family | Axioline F |
| Type | block modular |
| Mounting position | any (no temperature derating) |
| Scope of delivery | including bus base module and Axioline F connectors |
| Special properties | Extreme conditions version |
| Data management status | |
| Article revision | 07 |
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Maximum power dissipation for nominal condition | 3.4 W |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Current draw | max. 150 mA |
| typ. 120 mA | |
| Potentials: Supply for analog modules (UA) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 125 mA (4 current channels, 24 mA output, 500 Ω load) |
| typ. 60 mA (4 voltage channels, 10 V output) | |
| max. 85 mA (4 voltage channels, 10 V output) | |
| max. 110 mA (4 current channels, 20 mA output, 500 Ω load) | |
| Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
| Reverse polarity protection; Polarity protection diode | |
| Transient protection; Suppressor diode | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply of the local bus (UBus)/analog outputs | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V supply (I/O)/analog outputs | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: Analog outputs/functional ground | 500 V AC, 50 Hz, 1 min. |
| Connection technology | |
| Connection name | Axioline F connector |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Axioline F connector | |
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C (Standard, applications with UL approval, use in zone 2 potentially explosive area) |
| -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| ATEX | |
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | UL 20 ATEX 2441X |
| References to standards | EN IEC 60079-0, EN IEC 60079-7 |
| UKEX | |
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | PxCIMA22UKEX2701949X |
| References to standards | EN IEC 60079-0, EN IEC 60079-7 |
| IECEx | |
| Identification | Ex ec IIC T4 Gc |
| Certificate | IECEx ULD 20.0026X |
| References to standards | IEC 60079-0 Ed. 7, IEC 60079-7 Ed. 5.1 |
| UL, USA/Canada | |
| Identification | cULus |
| Certificate | E238705 |
| UL Ex, USA / Canada | |
| Identification | Class I, Zone 2, AEx ec IIC T4 |
| Class I, Division 2, Groups A, B, C, D, T4 | |
| Ex ec IIC T4 Gc X | |
| Certificate | E366272 |
| References to standards | UL 60079-0 Ed. 7 / CSA C22.2 NO. 60079-0 Ed. 4 |
| UL 60079-7 Ed. 5 / CSA C22.2 NO. 60079-7 Ed. 2 | |
| CCC / China-Ex | |
| Identification | Ex ec IIC T4 Gc |
| Certificate | , 2021122309114456 |
| References to standards | GB/T 3836.1-2021, GB/T 3836.3-2021 |
| Mounting type | DIN rail mounting |
| Mounting position | any (no temperature derating) |