Request QuoteProduct Overview
Equipped to handle rigorous industrial sensor arrays, the Phoenix Contact AXL F AI8 XC 1F I/O module provides robust analog data acquisition capabilities. Analog input modules are standard components in automated installations, translating fluctuating physical measurements into reliable digital data streams for system controllers. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): Yes
- Input, voltage (EF003205): Yes
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): Yes
- Resolution of the analogue inputs (EF003575): 16 Bit
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 8
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): Yes
- Analogue outputs configurable (EF008519): No
More info
▲Key Commercial Data
| Orderkey | 2701232 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 115 (C-6-2017) |
| GTIN | 4046356730495 |
| Weight per Piece (excluding packing) | 204.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C (Standard) |
|---|---|
| -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 204 g |
| Note on weight specifications | with connectors and bus base module |
Interfaces
| Designation | Axioline F local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
Axioline potentials
| Designation | Axioline F local bus supply (UBus) |
|---|---|
| Supply voltage | 5 V DC (via bus base module) |
| Current consumption | typ. 105 mA |
| max. 130 mA | |
| Power consumption | typ. 0.525 W |
| max. 0.65 W | |
| Designation | Supply for analog modules (UA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 35 mA |
| max. 45 mA | |
| Power consumption | max. 1.08 W |
| typ. 1.365 W (at UBusand UA) | |
| max. 1.605 W (at UBusand UA) | |
| Type of protection | Surge protection of the supply voltage |
| Polarity reversal protection of the supply voltage | |
| Transient protection supply voltage |
Analog inputs
| Description of the input | Differential inputs, voltage or current can be chosen separately |
|---|---|
| Input name | Analog inputs |
| Number of inputs | 8 |
| Connection method | Push-in connection |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded, twisted pair |
| A/D conversion time | 2 µs |
| Resolution A/D | 16 bit |
| Limit frequency (3 dB) | 30 Hz |
| 12 kHz (in fast mode) | |
| Type of protection | Transient protection of inputs |
| Overload protection of the current inputs | |
| Overload protection of the voltage inputs | |
| Data formats | IB IL, S7-compatible |
| Measured value representation | 16 bits (15 bits + sign bit) |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| -20 mA ... 20 mA | |
| Input resistance current input | 104 Ω (typical) |
| Voltage input signal | 0 V ... 5 V |
| -5 V ... 5 V | |
| 0 V ... 10 V | |
| -10 V ... 10 V | |
| Input resistance of voltage input | 268 kΩ (typical) |
| Common mode voltage range signal - ground | -50 V DC ... 50 V DC |
| Filtering | RFI filtering / passive TP 1st order |
| Input filter | 30 Hz, 12 kHz and mean-value generation (can be parameterized) |
Electrical isolation
| Test section | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
|---|---|
| Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g | |
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |