View larger
AXC 1050 XC 2701295 PHOENIX CONTACT Controller
AXC 1050 XC
2701295
PHOENIX CONTACT
1 Pcs.
Automation > PLC CPU-module
Control Systems (CST)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact AXC 1050 XC controller functions as a modular industrial automation device designed to manage complex control tasks, process data, and coordinate machine communication in factory environments. Programmable logic controllers of this class process input signals from sensors and issue precise commands to actuators across automated production lines.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Model (EF000010): Modular
- Processing time (1K, binary operation) (EF003004): 0.0013 ms
- Number of HW-interfaces industrial Ethernet (EF003020): 2
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces USB (EF003025): 1
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 1
- Number of analogue outputs (EF001995): 0
- Number of analogue inputs (EF001994): 0
- Number of digital inputs (EF001992): 0
More info
▲Key Commercial Data
| Orderkey | 2701295 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 76 (C-6-2017) |
| GTIN | 4055626000091 |
| Weight per Piece (excluding packing) | 225.600 g |
| Custom tariff number | 85371091 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (Observe derating as per user manual) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 58 kPa ... 106 kPa (up to 4500 m above mean sea level) |
| Shock | 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27 |
| Vibration (operation) | 5g |
Control system
| Engineering tool | PC WORX |
|---|---|
| PC WORX EXPRESS | |
| Programming languages supported | Programming in acc. with IEC 61131-3 |
| Diagnostics tool | DIAG+ |
| Configuration tool | Config+ Version 1.01 or later |
IEC 61131 runtime system
| Engineering tool | PC WORX |
|---|---|
| PC WORX EXPRESS | |
| Program memory | 2 Mbyte |
| Mass storage | 2 Mbyte |
| Retentive mass storage | 48 kByte (NVRAM) |
| Number of control tasks | 8 |
| Realtime clock | Yes |
Fieldbus function
| Amount of process data | max. 4096 Bit (Axioline F local bus (input)) |
|---|---|
| max. 4096 Bit (Axioline F local bus (output)) | |
| max. 32768 Bit (internal Modbus /TCP client) | |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 63 (observe current consumption) |
Data interfaces
| Interface | Axioline F local bus |
|---|---|
| Number | 1 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Interface | Service |
| Number | 1 |
| Connection method | Micro USB type B |
| Transmission speed | max. 115.2 kbps |
| Interface | Ethernet |
| Number | 2 |
| Connection method | RJ45 socket |
| Transmission speed | 10/100 Mbps |
PROFINET
| Device function | PROFINET controller, PROFINET device |
|---|---|
| Specification | Version 2.2 |
| Update rate | min. 32 ms (16 devices) |
| min. 32 ms (8 devices) | |
| min. 16 ms (4 devices) | |
| min. 8 ms (2 devices) | |
| min. 4 ms (1st device) |
Power supply
| Typical current consumption | 125 mA |
|---|---|
| Max. current consumption | 160 mA |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC |
| Residual ripple | ± 5 % |
| Power dissipation | max. 3 W |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Interference emission | Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class B |
| Immunity to surge | Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV |
| Immunity to burst | Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV |
| Immunity to EF | Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
| Immunity to ESD | Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge |
| Immunity to conducted interference | Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V |
| Vibration (storage/transport) | 5g |
| Shock | 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27 |
| Vibration (operation) | 5g |
| Shock (operation) | 10g (Bump endurance test according to DIN EN 60068-2-27) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |