View larger
Images are for illustrative purposes only. Please refer to data sheet for details
AXC 1050 2700988 PHOENIX CONTACT Controller
AXC 1050
2700988
PHOENIX CONTACT
1 Pcs.
Controller
Axial control for the Axioline direct I/O control system. With 2 Ethernet interfaces and programmability in accordance with IEC 61131-3. Complete with connector and labeling surface.
Automation > PLC CPU-module
Control Systems (CST)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A controller such as the Phoenix Contact AXC 1050 2700988 is installed within automation networks to execute control logic, process sensor data, and coordinate field devices in manufacturing machinery and processing plants.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2700988
- Packing unit: 1 pc
- Catalog page: Page 76 (C-6-2017)
- GTIN: 4046356731195
- Weight per Piece (excluding packing): 225.600 g
- Custom tariff number: 85371091
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Width: 45 mm
- Height: 125.9 mm
- Depth: 74 mm
- Degree of protection: IP20
- Ambient temperature (operation): -25 °C ... 60 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Permissible humidity (operation): 5 % ... 95 % (according to DIN EN 61131-2)
- Permissible humidity (storage/transport): 5 % ... 95 % (according to DIN EN 61131-2)
More info
▲Key Commercial Data
| Orderkey | 2700988 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 76 (C-6-2017) |
| GTIN | 4046356731195 |
| Weight per Piece (excluding packing) | 225.600 g |
| Custom tariff number | 85371091 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 58 kPa ... 106 kPa (up to 4500 m above mean sea level) |
| Shock | 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27 |
| Vibration (operation) | 5g |
Control system
| Engineering tool | PC WORX |
|---|---|
| PC WORX EXPRESS | |
| Programming languages supported | Programming in acc. with IEC 61131-3 |
| Diagnostics tool | DIAG+ |
| Configuration tool | Config+ Version 1.01 or later |
IEC 61131 runtime system
| Engineering tool | PC WORX |
|---|---|
| PC WORX EXPRESS | |
| Program memory | 2 Mbyte |
| Mass storage | 2 Mbyte |
| Retentive mass storage | 48 kByte (NVRAM) |
| Number of control tasks | 8 |
| Realtime clock | Yes |
Fieldbus function
| Amount of process data | max. 4096 Bit (Axioline F local bus (input)) |
|---|---|
| max. 4096 Bit (Axioline F local bus (output)) | |
| max. 32768 Bit (internal Modbus /TCP client) | |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 63 (observe current consumption) |
Data interfaces
| Interface | Axioline F local bus |
|---|---|
| Number | 1 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Interface | Ethernet |
| Number | 2 |
| Connection method | RJ45 socket |
| Transmission speed | 10/100 Mbps |
| Interface | Service |
| Number | 1 |
| Connection method | Micro USB type B |
| Transmission speed | max. 115.2 kbps |
PROFINET
| Device function | PROFINET controller, PROFINET device |
|---|---|
| Specification | Version 2.2 |
| Update rate | min. 32 ms (16 devices) |
| min. 32 ms (8 devices) | |
| min. 16 ms (4 devices) | |
| min. 8 ms (2 devices) | |
| min. 4 ms (1st device) |
Power supply
| Typical current consumption | 125 mA |
|---|---|
| Max. current consumption | 160 mA |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC |
| Residual ripple | ± 5 % |
| Power dissipation | max. 3 W |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Interference emission | Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class B |
| Immunity to surge | Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV |
| Immunity to burst | Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV |
| Immunity to EF | Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
| Immunity to ESD | Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge |
| Immunity to conducted interference | Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V |
| Vibration (storage/transport) | 5g |
| Shock | 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27 |
| Vibration (operation) | 5g |
| Shock (operation) | 10g (Bump endurance test according to DIN EN 60068-2-27) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |