View larger
C-UB/E 2763701 PHOENIX CONTACT Surge protection device
C-UB/E
2763701
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact C-UB/E functions as a dedicated surge protection device engineered to safeguard industrial interface links against harmful electrical surges. Placed strategically within signal pathways, this plug-type suppressor prevents transient overvoltages from propagating into delicate measurement and control instrumentation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2763701
- Packing unit: 10 pc
- Catalog page: Page 177 (C-4-2017)
- GTIN: 4017918065638
- Weight per Piece (excluding packing): 102.400 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 25.4 mm
- Width: 25.4 mm
- Depth: 80 mm
- Ambient temperature (operation): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: Aluminum
- Mounting type: Connection-specific intermediate plugging
- Type: Attachment plug
More info
▲Key Commercial Data
| Orderkey | 2763701 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 177 (C-4-2017) |
| GTIN | 4017918065638 |
| Weight per Piece (excluding packing) | 102.400 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 80 °C |
|---|---|
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | Aluminum |
|---|---|
| Mounting type | Connection-specific intermediate plugging |
| Type | Attachment plug |
| Direction of action | Line-Shield/Earth Ground |
Additional descriptions
| Note | To meet the discharge conditions for DC voltages, please note the following information: "The surge protective device should be used together with a transmitter unit, which shuts down in the event of a short-circuit." |
|---|
Protective circuit
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 180 V DC |
| 130 V AC | |
| Rated current | 3.5 A (25 °C) |
| Operating effective current ICat UC | ≤ 1 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Nominal discharge current In(8/20) µs (line-shield) | 5 kA |
| Nominal discharge current In(8/20) µs (shield-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-shield) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 470 V |
| Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 590 V |
| Output voltage limitation at 1 kV/µs (shield-earth) spike | ≤ 470 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 33 V |
| Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 33 V |
| Output voltage limitation at 1 kV/µs (shield-earth) static | ≤ 33 V |
| Residual voltage at In(line-earth) | ≤ 160 V (1.5 m cable) |
| Residual voltage at In(line-shield) | ≤ 55 V |
| Residual voltage at In(shield-earth) | ≤ 160 V (1.5 m cable) |
| Voltage protection level Up(line-earth) | ≤ 500 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-shield) | ≤ 700 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(shield-ground) | ≤ 500 V (C2 - 10 kV / 5 kA) |
| Response time tA | ≤ 100 ns |
| Input attenuation aE, asym. | typ. 0.1 dB (≤ 100 MHz/50 Ω) |
| Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system | typ. 1 GHz |
| Standing wave ratio SWR in a 50 Ω system | typ. 1.3 (≤ 150 MHz) |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) | 300 W (VSWR = 1.1) |
| 80 W (VSWR = ∞) | |
| Capacity asymmetrical (shield) | typ. 6 pF |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C3 - 100 A | |
| D1 - 2.5 kA | |
| Impulse durability (line-shield) | C2 - 10 kV/5 kA |
| C3 - 100 A | |
| D1 - 2.5 kA |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |