PHOENIX CONTACT MNT-1 D MNT-1 D 2882200 PHOENIX CONTACT Attachment plug with surge protection for mains sockets, optical power and f.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MNT-1 D 2882200 PHOENIX CONTACT Attachment plug with surge protection for mains sockets, optical power and f..

MNT-1 D

2882200

PHOENIX CONTACT

1 Pcs.

Attachment plug with surge protection for mains sockets, optical power and fault display. For country-specific use in: D, A, I, NL, S, E, N, FIN Adapter with surge protection for power outlets, optical power and fault indication. Country-specific usable in: D, A, I, NL, S, E, N, FIN

Automation > Surge protection device for terminal equipment
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact part number MNT-1 D (model MNT-1 D 2882200 PHOENIX CONTACT Attachment plug with surge protection for mains sockets...) serves as an attachment plug equipped with integrated surge protection, designed to shield connected mains-powered devices from transient overvoltages. These plug-in units offer convenient point-of-use defense for sensitive equipment.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Max. continuous voltage AC (EF004198): 360 V
  • Voltage protection level L-N (EF004236): 1.5 kV
  • With remote signalling contact (EF000422): No
  • Signalling at the device (EF004241): Optic
  • Category type 3 (EF004231): Yes
  • Degree of protection (IP) (EF005474): IP20

More info

▲

Dimensions

Height 76 mm
Width 56 mm
Depth 78 mm

Ambient conditions

Ambient temperature (storage/transport) -25 °C ... 75 °C
Ambient temperature (operation) -25 °C ... 75 °C

General

Housing material PA 6
Flammability rating according to UL 94 V-0
Color jet black RAL 9005
Standards for cearances and creepage distances EN 60664-1
IEC 60664-1
IEC 61643-1
EN 61643-11
Type Attachment plug
Mounting type Plugging into the mains socket
For country-specific use in D, A, NL, E, S, FIN, TR
Direction of action L(N)-PE

Protective circuit

IEC test classification III
T3
EN type T3
Nominal voltage UN 230 V AC
Arrester rated voltage UC(L-N) 275 V AC
Arrester rated voltage UC(L-PE) 360 V AC
Arrester rated voltage UC(N-PE) 360 V AC
Nominal frequency fN 50 Hz (60 Hz)
Standby power consumption PC ≤ 1 VA
Residual current IPE ≤ 5 µA
Nominal discharge current In(8/20) µs 3 kA (> 5x)
Combination wave UOC 4 kV
Energy absorption symmetrical 140 J (L-N (L))
Enery absorption, asymmetrical 220 J (L(N)-PE)
Voltage protection level Up(L-N) ≤ 1.2 kV
Voltage protection level Up(L-PE) ≤ 1.5 kV
Voltage protection level Up(N-PE) ≤ 1.5 kV
Response time tA(L-N) ≤ 25 ns
Response time tA(L-PE) ≤ 100 ns
Response time tA(N-PE) ≤ 100 ns
Max. required back-up fuse 16 A AC (gG / B / C)
Surge protection fault message optical

Non-heating apparatus connection, power supply

Connection method Grounding plug/socket
Connection type IN Grounding plug
Connection type OUT Grounding socket

Standards and Regulations

Standards/specifications IEC 61643-11 2011
EN 61643-11 2012