CN-LAMBDA/4-5.9-BB 2838490 PHOENIX CONTACT Surge protection device
CN-LAMBDA/4-5.9-BB
2838490
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact Surge protection device part number CN-LAMBDA/4-5.9-BB is a coaxial lightning surge arrester engineered to protect high-frequency radio frequency and telecommunication systems from transient voltage impulses without signal degradation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2838490
- Packing unit: 1 pc
- Catalog page: Page 179 (C-4-2017)
- GTIN: 4046356285629
- Weight per Piece (excluding packing): 140.190 g
- Custom tariff number: 85363010
- Country of origin: US (United States)
- Height: 38 mm
- Width: 26.1 mm
- Depth: 60 mm
- Ambient temperature (operation): -40 °C ... 90 °C
- Degree of protection: IP68
- Housing material: Brass (CuZn)
- Color: nickel
- Mounting type: Connection-specific intermediate plugging
- Type: Attachment plug
More info
▲Key Commercial Data
| Orderkey | 2838490 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 179 (C-4-2017) |
| GTIN | 4046356285629 |
| Weight per Piece (excluding packing) | 140.190 g |
| Custom tariff number | 85363010 |
| Country of origin | US (United States) |
General
| Housing material | Brass (CuZn) |
|---|---|
| Color | nickel |
| Mounting type | Connection-specific intermediate plugging |
| Type | Attachment plug |
| Number of positions | 1 |
| Direction of action | Line-Shield/Earth Ground |
Protective circuit
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| VDE requirement class | C2 |
| C3 | |
| D1 | |
| Rated current | 5 A (25 °C) |
| Nominal discharge current In(8/20) µs (line-earth) | 50 kA |
| Nominal discharge current In(8/20) µs (line-shield) | 50 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | ≤ 20 kA |
| Total discharge current Itotal(8/20) µs | 60 kA |
| Total discharge current Itotal(10/350) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 60 kA |
| Max. discharge current Imax(8/20) µs maximum (line-shield) | 60 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 11 V (6 kV / 3 kA) |
| Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 11 V (6 kV / 3 kA) |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 11 V (6 kV / 3 kA) |
| Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 11 V (6 kV / 3 kA) |
| Voltage protection level Up(line-earth) | ≤ 11 V (6 kV / 3 kA) |
| Voltage protection level Up(line-shield) | ≤ 11 V (6 kV / 3 kA) |
| Input attenuation aE, asym. | typ. 0.05 dB (≤ 0.15 dB) |
| Frequency range | 2.4 GHz ... 5.9 GHz |
| Standing wave ratio SWR in a 50 Ω system | typ. 1.1 (≤ 1.20 (2.4 GHz...5.9 GHz)) |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) | ≤ 500 W |
| ≤ 4 kW (peak) | |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA | |
| Impulse durability (line-shield) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Connection data
| Connection method | N Connector |
|---|---|
| Connection method IN | N connector, female |
| Connection method OUT | N connector, female |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |