View larger
C-UFB- 5DC/E 75 2763604 PHOENIX CONTACT Surge protection device
C-UFB-5DC/E 75
2763604
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protect delicate control loops and signal lines from unexpected voltage surges with the Phoenix Contact C-UFB-5DC/E 75 surge protection device. These inline components are widely utilized in automation architectures to safeguard automation hardware and field instruments against high-energy transients induced by switching operations or lightning. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2763604
- Packing unit: 10 pc
- Catalog page: Page 177 (C-4-2017)
- GTIN: 4017918347772
- Weight per Piece (excluding packing): 102.800 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 25.4 mm
- Width: 25.4 mm
- Depth: 93 mm
- Ambient temperature (operation): -40 °C ... 80 °C
- Degree of protection: IP20
- Housing material: Aluminum
- Color: black
- Standards for cearances and creepage distances: VDE 0110-1
- Mounting type: Connection-specific intermediate plugging
More info
▲Key Commercial Data
| Orderkey | 2763604 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 177 (C-4-2017) |
| GTIN | 4017918347772 |
| Weight per Piece (excluding packing) | 102.800 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | Aluminum |
|---|---|
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | Connection-specific intermediate plugging |
| Type | Attachment plug |
| Direction of action | Line-Shield/Earth Ground |
Protective circuit
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 5 V DC |
| Rated current | 185 mA (25 °C) |
| Operating effective current ICat UC | ≤ 300 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Nominal discharge current In(8/20) µs (line-shield) | 10 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 500 V |
| Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 35 V |
| Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 15 V |
| Residual voltage at In(line-shield) | ≤ 12 V |
| Voltage protection level Up(line-earth) | ≤ 500 V (C1 - 1 kV/500 A) |
| ≤ 500 V (C3 - 10 A) | |
| Voltage protection level Up(line-shield) | ≤ 25 V (C3 - 10 A) |
| ≤ 55 V (C1 - 1 kV/500 A) | |
| Response time tA(line-earth) | ≤ 100 ns |
| Response time tA (line-shield) | ≤ 500 ns |
| Input attenuation aE, asym. | 1.3 dB (≤ 5 MHz) |
| Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system | typ. 80 MHz |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |