View larger
IB IL TEMP 2 UTH-PAC 2861386 PHOENIX CONTACT Inline terminal
IB IL TEMP 2 UTH-PAC
2861386
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact inline terminal IB IL TEMP 2 UTH-PAC operates as a modular input device designed to interface thermocouple sensors with industrial automation systems. This component acquires temperature measurements and transmits the converted data across local bus architectures for system monitoring.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Width: 12.2 mm
- Height: 136.8 mm
- Depth: 71.5 mm
- Note on dimensions: Housing dimensions
- Note on application Note on application: Only for industrial use
- Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China.
- Inline local bus Number of interfaces: 2
- Connection method: Inline data jumper
- Transmission speed: 500 kbps
- Module ID code (dec.): 127
- ID code (hex): 7F
- Length code (hex): 02
- Length code (dec): 02
- Process data channel: 32 bit
- Input address area: 4 Byte
- Output address area: 4 Byte
More info
▲| Dimensional drawing | |
| Width | 12.2 mm |
| Height | 136.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Inline local bus | |
| Number of interfaces | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Module | |
| ID code (dec.) | 127 |
| ID code (hex) | 7F |
| Length code (hex) | 02 |
| Length code (dec) | 02 |
| Process data channel | 32 bit |
| Input address area | 4 Byte |
| Output address area | 4 Byte |
| Register length | 32 bit |
| Required parameter data | 6 Byte |
| Required configuration data | 4 Byte |
| Analog | |
| Input name | Analog UTH inputs |
| Description of the input | Inputs for thermocouples or linear voltage |
| Number of inputs | 2 (Thermocouples or linear voltage) |
| Connection method | Inline connector |
| Connection technology | 2-conductor |
| Note regarding the connection technology | Shielded compensating line for TC with encapsulated sensors |
| A/D conversion time | typ. 120 µs (per channel) |
| Sensor types that can be used (TC) | U, T, L, J, E, K, N, S, R, B, C, W, HK |
| Measuring principle | Successive approximation |
| Measured value representation | 16 bits (15 bits + sign bit) |
| Process data update | max. 30 ms (For both channels) |
| Protective circuit | Surge protection (TC channels); up to ±40 V |
| Product type | I/O component |
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connector and labeling field |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Failure of or insufficient communications power ULI/O error message sent to the bus coupler | |
| I/O error Error message in the process data | |
| User error Error message in the process data | |
| Data management status | |
| Article revision | 11 |
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Maximum power dissipation for nominal condition | 0.9 W |
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 60 mA |
| typ. 43 mA | |
| Potentials: Supply of analog modules (UANA) | |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 18 mA |
| typ. 11 mA | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Connection technology | |
| Connection name | Inline connector |
| Conductor connection | |
| Connection method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Inline connector | |
| Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |