An Inline ME terminal from Phoenix Contact, the IB IL AI 2/SF-ME processes analog input signals from field instrumentation to support industrial monitoring applications. Input terminals aggregate data streams for efficient transmission into the primary automation controller network.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): Yes
- Input, voltage (EF003205): Yes
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): Yes
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 2
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): Yes
- Analogue outputs configurable (EF008519): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
More info
▲Key Commercial Data
| Orderkey | 2863944 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 158 (C-6-2017) |
| GTIN | 4017918962654 |
| Weight per Piece (excluding packing) | 86.200 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 12.2 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 86.2 g |
| Note on weight specifications | with connector |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Failure of the internal I/O supply Yes |
| Peripheral fault Error message in the process data | |
| User error Error message in the process data |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 45 mA |
| max. 60 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 13 mA |
| max. 18 mA | |
| Power consumption | typ. 662 mW |
Analog inputs
| Description of the input | Single-ended inputs, voltage or current |
|---|---|
| Input name | Analog inputs |
| Number of inputs | 2 |
| Connection method | Inline connector |
| Connection technology | 2-wire |
| A/D conversion time | typ. 120 µs (per channel) |
| Limit frequency (3 dB) | 40 Hz |
| Type of protection | Surge protection |
| Data formats | IB IL, IB ST, IB RT, standardized representation |
| Measuring principle | Successive approximation |
| Measured value resolution | 13 bits (12 bits + sign bit) |
| Measured value representation | 13 bits (12 bits + sign bit) |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| -20 mA ... 20 mA | |
| Input resistance current input | 50 Ω (Shunt) |
| Voltage input signal | 0 V ... 10 V |
| -10 V ... 10 V | |
| Input resistance of voltage input | > 220 kΩ |
| Common mode voltage range signal - ground | 40 V (between current input and functional earth ground) |
Electrical isolation
| Test section | 7.5 V supply (bus logic), 24 V supply UANA/ I/O 500 V AC 50 Hz 1 min. |
|---|---|
| 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min. | |
| I/O / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |