PHOENIX CONTACT RAD-AO4-IFS RAD-AO4-IFS 2901538 PHOENIX CONTACT I/O extension module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

RAD-AO4-IFS 2901538 PHOENIX CONTACT I/O extension module

RAD-AO4-IFS

2901538

PHOENIX CONTACT

1 Pcs.

I/O extension module Radioline: I/O expansion module, 4 analog current or voltage outputs (0/4 mA ... 20 mA, 0 V... 10 V)

Automation > Fieldbus, decentr. periphery - analogue I/O module
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Providing seamless expansion capabilities, the Phoenix Contact RAD-AO4-IFS is an I/O extension module used to scale analog output channels within remote wireless or serial automation networks. Such devices allow distributed systems to interface smoothly with centralized control stations.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Voltage type (supply voltage) (EF002991): DC
  • Input, current (EF003204): No
  • Input, voltage (EF003205): No
  • Input, resistor (EF003206): No
  • Input, resistance thermometer (EF003207): No
  • Input, thermocouple (EF003208): No
  • Input signal, configurable (EF003209): No
  • Output, current (EF003212): No
  • Output, voltage (EF003213): No
  • Output signal configurable (EF003214): No
  • Number of analogue inputs (EF001994): 0
  • Number of analogue outputs (EF001995): 0
  • Analogue inputs configurable (EF008518): No
  • Analogue outputs configurable (EF008519): No
  • Number of HW-interfaces industrial Ethernet (EF003020): 0
  • Number of interfaces PROFINET (EF006932): 0

More info

▲

Key Commercial Data

Orderkey2901538
Packing unit1 pc
Catalog pagePage 463 (C-6-2017)
GTIN4046356609166
Weight per Piece (excluding packing)174.400 g
Custom tariff number85177000
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width17.5 mm
Height113 mm
Depth114.5 mm
Dimensional drawing

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C (>55°C derating)
-40 °F ... 158 °F (>131°F derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
-40 °F ... 185 °F
Permissible humidity (operation)20 % ... 85 %
Permissible humidity (storage/transport)20 % ... 85 %
Altitude2000 m
Vibration (operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
Shock16g, 11 ms

General

Overvoltage categoryII
Mounting positionany
Assembly instructionson standard DIN rail NS 35 in accordance with EN 60715
Degree of pollution2
Housing materialPA 6.6-FR
Flammability rating according to UL 94V0
MTTF999 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
404 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
156 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day))

Supply

Supply voltage range19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption≤ 115 mA (At 24 V DC, at 25°C)
Transient surge protectionYes

Analog outputs

Number of outputs4
Voltage output signal0 V ... 10 V
Max. voltage output signalapprox. 10.83 V
Load≥ 10 kΩ
Precisiontyp. 0.5 % (Voltage output)
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signalapprox. 21.67 mA
Load≤ 500 Ω
Precision≤ 0.02 % (at 25 °C)
Resolution16 bit
Temperature coefficient, typical0.0025 %/K (at -40 °C ... +70 °C)
Behavior of the outputs (adjustable via DIP switch)Hold / Reset
Protective circuitTransient protection of outputs

Electrical isolation

Analog I/O50 V (Rated insulation voltage (in each case between the TBUS analog outputs / supply, reinforced insulation according to EN 61010))

Test voltage

Analog I/O1.5 kV AC (50 Hz, 1 min.)

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Tightening torque0.6 Nm
Screw threadM3

Status indicator

Status displayGreen LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Standard designationEMC Directive 2014/30/EU
Standards/regulationsEN 61000-6-2
Standard designationEMC Directive 2014/30/EU
Standards/regulationsEN 61000-6-4
Standard designationEx Directive (ATEX)
Standards/regulationsEN 60079-0
Standard designationEx Directive (ATEX)
Standards/regulationsEN-60079-15
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2
Flammability rating according to UL 94V0
Shock16g, 11 ms
Vibration (operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc
IECExEx nA IIC T4 Gc
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, IIC T4
Noxious gas testISA-S71.04-1985 G3 Harsh Group A

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Articles in set

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.