View larger
RAD-AO4-IFS 2901538 PHOENIX CONTACT I/O extension module
RAD-AO4-IFS
2901538
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing seamless expansion capabilities, the Phoenix Contact RAD-AO4-IFS is an I/O extension module used to scale analog output channels within remote wireless or serial automation networks. Such devices allow distributed systems to interface smoothly with centralized control stations.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
More info
▲Key Commercial Data
| Orderkey | 2901538 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 463 (C-6-2017) |
| GTIN | 4046356609166 |
| Weight per Piece (excluding packing) | 174.400 g |
| Custom tariff number | 85177000 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (>55°C derating) |
| -40 °F ... 158 °F (>131°F derating) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| -40 °F ... 185 °F | |
| Permissible humidity (operation) | 20 % ... 85 % |
| Permissible humidity (storage/transport) | 20 % ... 85 % |
| Altitude | 2000 m |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Shock | 16g, 11 ms |
General
| Overvoltage category | II |
|---|---|
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Degree of pollution | 2 |
| Housing material | PA 6.6-FR |
| Flammability rating according to UL 94 | V0 |
| MTTF | 999 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 404 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| 156 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
Supply
| Supply voltage range | 19.2 V DC ... 30.5 V DC (DIN rail connector) |
|---|---|
| Max. current consumption | ≤ 115 mA (At 24 V DC, at 25°C) |
| Transient surge protection | Yes |
Analog outputs
| Number of outputs | 4 |
|---|---|
| Voltage output signal | 0 V ... 10 V |
| Max. voltage output signal | approx. 10.83 V |
| Load | ≥ 10 kΩ |
| Precision | typ. 0.5 % (Voltage output) |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Max. current output signal | approx. 21.67 mA |
| Load | ≤ 500 Ω |
| Precision | ≤ 0.02 % (at 25 °C) |
| Resolution | 16 bit |
| Temperature coefficient, typical | 0.0025 %/K (at -40 °C ... +70 °C) |
| Behavior of the outputs (adjustable via DIP switch) | Hold / Reset |
| Protective circuit | Transient protection of outputs |
Electrical isolation
| Analog I/O | 50 V (Rated insulation voltage (in each case between the TBUS analog outputs / supply, reinforced insulation according to EN 61010)) |
|---|
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Tightening torque | 0.6 Nm |
| Screw thread | M3 |
Status indicator
| Status display | Green LED (supply voltage, PWR) |
|---|---|
| Green LED (bus communication, DAT) | |
| Red LED (periphery error, ERR) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-2 |
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-4 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN 60079-0 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN-60079-15 |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Flammability rating according to UL 94 | V0 |
| Shock | 16g, 11 ms |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc |
| IECEx | Ex nA IIC T4 Gc |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T4A | |
| Class I, Zone 2, IIC T4 | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |