View larger
RAD-AI4-IFS 2901537 PHOENIX CONTACT I/O extension module
RAD-AI4-IFS
2901537
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact RAD-AI4-IFS I/O extension module expands wireless and modular industrial communication stations with additional signal channels. Extension units allow automation networks to scale seamlessly when extra measurement points are added to a plant floor. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
More info
▲Key Commercial Data
| Orderkey | 2901537 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 462 (C-6-2017) |
| GTIN | 4046356610476 |
| Weight per Piece (excluding packing) | 203.700 g |
| Custom tariff number | 85177000 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (>55°C derating) |
| -40 °F ... 158 °F (>131°F derating) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| -40 °F ... 185 °F | |
| Permissible humidity (operation) | 20 % ... 85 % |
| Permissible humidity (storage/transport) | 20 % ... 85 % |
| Altitude | 2000 m |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Shock | 16g, 11 ms |
General
| Overvoltage category | II |
|---|---|
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Degree of pollution | 2 |
| Housing material | PA 6.6-FR |
| Flammability rating according to UL 94 | V0 |
| MTTF | 771 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 351 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| 136 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
Supply
| Supply voltage range | 19.2 V DC ... 30.5 V DC (DIN rail connector) |
|---|---|
| Max. current consumption | ≤ 120 mA (At 24 V DC, at 25°C) |
| Transient surge protection | Yes |
Analog inputs
| Number of inputs | 4 |
|---|---|
| Current input signal | 0 mA ... 20 mA (can be set via DIP switches) |
| 4 mA ... 20 mA (can be set via DIP switches) | |
| Max. current input signal | 22 mA |
| Input resistance current input | < 70 Ω |
| Precision | ≤ 0.02 % (at 25 °C) |
| Temperature coefficient, typical | 0.0025 %/K (at -40 °C ... +70 °C) |
| Supply voltage | ≥ 12 V DC (For passive sensors (via terminal PWR1, +I1)) |
| Resolution | 16 bit |
| Protective circuit | Short-circuit and overload protection |
Electrical isolation
| Analog I/O | 50 V (Rated insulation voltage (in each case between the TBUS analog outputs / supply, reinforced insulation according to EN 61010)) |
|---|
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Tightening torque | 0.6 Nm |
| Screw thread | M3 |
Status indicator
| Status display | Green LED (supply voltage, PWR) |
|---|---|
| Green LED (bus communication, DAT) | |
| Red LED (periphery error, ERR) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-2 |
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-4 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN 60079-0 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN-60079-15 |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Flammability rating according to UL 94 | V0 |
| Shock | 16g, 11 ms |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc |
| IECEx | Ex nA IIC T4 Gc |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T4A | |
| Class I, Zone 2, IIC T4 | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |